MAKING MODERN LIVING POSSIBLE V V LT AQUA Drive Cascade Controller Options MCO 101/102 Operating Instructions...
Page 2
11-90 kW 110-250 315-1000 525-600 0.75-7.5 11-90 kW 525-690 11-37 kW 45-400 450-1200 1400 kW High voltage may be present even when the warning LED display lights are off. Discharge Time ® MI38C402 - VLT is a registered Danfoss trademark...
Page 3
® Safety AQUA Drive MCO 101/MCO 102 ® MI38C402 - VLT is a registered Danfoss trademark...
4.2.2 Manual Pump Control 4.2.3 Runtime Balancing 4.2.4 Pump Spin for Unused Pumps 4.2.5 Total Lifetime Hours 4.2.6 Alternation of the Lead Pump 4.2.7 Staging/De-staging in Mixed Pump Configurations 4.2.8 Override Staging/De-staging ® MI38C402 - VLT is a registered Danfoss trademark...
MCO 101 (Extended Cascade Controller) The purpose of these operating instructions is to describe • MCO 102 (Advanced Cascade Controller) the Danfoss Cascade Controller Options MCO 101 and MCO 102. For further information, see 2 Application Types. The operating instructions contain information about: The Extended Cascade Controller can be used in two •...
Page 7
+Documentation.htm for listings. • Optional equipment may change some of the procedures described. Reference the instructions supplied with those options for specific requirements. Contact the local Danfoss supplier or visit the Danfoss website: www.danfoss.com/ BusinessAreas/DrivesSolutions/Documentations/ Technical+Documentation.htm, for downloads or additional information.
Use of the extended cascade option MCO 101 as an extension of the built-in basic cascade in the frequency converter In applications already controlled by the built-in Cascade Controller in parameter group 25-**, the option card can ® MI38C402 - VLT is a registered Danfoss trademark...
Page 9
The variable speed pump provides the finer level of control needed between the stages. The direct online pumps are staged or de-staged depending on the feedback. Illustration 2.3 Fixed Speed Pump Configuration Example ® MI38C402 - VLT is a registered Danfoss trademark...
Motor / Pump 1 Motor / Pump 2 Transmitter 0 - 10 V 0 - 20 mA or 4 - 20 mA 100% 100% 100% Illustration 2.4 Basic Wiring Principle (Example) ® MI38C402 - VLT is a registered Danfoss trademark...
All variable speed pumps and frequency converters must 27-70.0 RELAY 1 → [73] Pump 2 to Mains be the same size. Fixed speed pumps may be of different 27-70.1 RELAY 2 → [74] Pump 3 to Mains sizes. ® MI38C402 - VLT is a registered Danfoss trademark...
Illustration 2.7 Valid Configuration Example NOTICE Invalid configurations, like in Illustration 2.8, will still run but will not stage on all pumps. This feature allows for limited operation if a pump fails or is interlocked. ® MI38C402 - VLT is a registered Danfoss trademark...
27-70.9 RELAY 10 → [72] Pump 1 to Mains via parameter group 5-1* Digital Inputs). To use for example an electro-mechanical flow switch to detect a no 27-70.10 RELAY 11 → [73] Pump 2 to Mains ® MI38C402 - VLT is a registered Danfoss trademark...
Fit the extended cradle and terminal cover. Remount the LCP. The MCO 101 option includes 3 pieces of change-over Connect power to the frequency converter. contacts and can be fitted into option slot B. ® MI38C402 - VLT is a registered Danfoss trademark...
Page 16
Illustration 3.3 Mounting of Cables WARNING Do not combine low voltage parts and PELV systems (see Illustration 3.4. Illustration 3.4 Incorrect and Correct Relay Wiring Live part PELV Table 3.4 Legend to Correct Relay Wiring ® MI38C402 - VLT is a registered Danfoss trademark...
Tools required Some items are needed for the installation of a C option mounting kit (depending on the enclosure): Illustration 3.5 Enclosure A2, A3 (and B3) 40 mm (only one C option) ® MI38C402 - VLT is a registered Danfoss trademark...
Page 18
Fit the extended cradle and terminal cover. Remount the LCP. Connect power to the frequency converter. Wiring the Terminals Illustration 3.7 Advanced Cascade Controller MCO 102 Terminal Connections, 8 Relays ® MI38C402 - VLT is a registered Danfoss trademark...
1-00 Configuration Mode to [0] Open Loop and Define relays in parameter group 27-7* 3-15 Reference 1 Source to selection [7] Pulse input Connections 29 and 5-13 Terminal 29 Digital Input to [32] Pulse input. ® MI38C402 - VLT is a registered Danfoss trademark...
Set the values The stage on and de-stage off speed can be auto tuned through: during automation or set manually. If Auto-tune is enabled ® MI38C402 - VLT is a registered Danfoss trademark...
If a pump is taken offline through 27-02 Manual Pump individual pumps. Select a specific pump to view the Control, the cascade Controller attempts to compensate for the offline pumps as follows: ® MI38C402 - VLT is a registered Danfoss trademark...
Controller balances running hours by alternating the lead pump. Alternation of lead pumps can also be forced manually e.g. through 27-54 Alternation At Time of Day or through a digital input. Use alternation time parameters if the system ® MI38C402 - VLT is a registered Danfoss trademark...
27-24 Destaging Delay. If the system demand continues to drop the system will enter sleep mode. Operating Range for the Staging Delay time (27-23 Staging Delay), a fixed speed pump will be turned on. ® MI38C402 - VLT is a registered Danfoss trademark...
• Enable Flow Compensation in 22-80 Flow Compensation • Program the Pressure at No-Flow Speed in 22-87 Pressure at No-Flow Speed • Program the uncompensated setpoint (e.g. in 20-21 Setpoint 1) ® MI38C402 - VLT is a registered Danfoss trademark...
[30] Ext. Closed Loop 1 [31] Ext. Closed Loop 2 3-15 Reference 1 Source [32] Ext. Closed Loop 3 Option: Function: Select the reference input to be used for the first reference signal. ® MI38C402 - VLT is a registered Danfoss trademark...
Page 26
[166] Remote ref active Stand-by / no warning [167] Start command act. Running [168] Hand mode Running / no warning [169] Auto mode Run on ref/no warn [180] Clock Fault Alarm ® MI38C402 - VLT is a registered Danfoss trademark...
Offline - On The pump is not available for use by the operating hours for each connected Drive Cascade Controller, and the pump is pump. connected to mains and is running ® MI38C402 - VLT is a registered Danfoss trademark...
% of Max Reference, see Spare Pump Turned on last, turned off ® 21-12 Ext. 1 Maximum Reference in the VLT first. AQUA Drive Programming Guide for further information. ® MI38C402 - VLT is a registered Danfoss trademark...
Page 30
Override operation may be disabled by setting this parameter to 100%. NOTICE Illustration 5.4 In master-follower applications the override limit is used as wake-up condition. See 6.1 Master/Follower for further information. ® MI38C402 - VLT is a registered Danfoss trademark...
If the lead pump is operating above normal operating band before a pump will be Stage On Speed for the time specified turned off to save energy. Energy savings may be ® MI38C402 - VLT is a registered Danfoss trademark...
27-34 Stage Off Speed [Hz] soft starter controlled pumps. Range: Function: Size [ 0.0 - If the lead pump is operating below related 50 Hz] Stage Off Speed for the time specified in ® MI38C402 - VLT is a registered Danfoss trademark...
If 27-40 Auto Tune Staging Settings is [1] Enabled will be kept up to date with new automatically calculated values. If 27-43 Staging Threshold and 27-44 Destaging ® MI38C402 - VLT is a registered Danfoss trademark...
This provides time for the contactors [65] Reset Counter B to switch while both pumps are stopped. [66] Sleep Mode [78] Reset Preventive Maintenance Word [80] PTC Card 1 [85] Latched Pump Derag ® MI38C402 - VLT is a registered Danfoss trademark...
Page 35
Reset Preventive Maintenance Word [80] PTC Card 1 [80] PTC Card 1 [85] Latched Pump Derag [85] Latched Pump Derag [120] Lead Pump Start [120] Lead Pump Start [121] Lead Pump Alternation ® MI38C402 - VLT is a registered Danfoss trademark...
Page 36
Latched Pump Derag [120] Lead Pump Start [120] Lead Pump Start [121] Lead Pump Alternation [121] Lead Pump Alternation [130] Pump 1 Interlock [130] Pump 1 Interlock [131] Pump 2 Interlock ® MI38C402 - VLT is a registered Danfoss trademark...
Current % of Total Capacity is a readout parameter that shows the system operating point as a % capacity of total system capacity. 100% means all pumps are on at full speed. Units: % Range: Function: [0 - 0 %] ® MI38C402 - VLT is a registered Danfoss trademark...
TRUE 27-04 Lifetime Hours TRUE 27-1* Configuration Reset Current [0] Do not set- Cascade 2 set- FALS 27-19 Runtime Hours reset TRUE Uint8 27-10 Controller null Uint8 27-2* Bandwidth Settings ® MI38C402 - VLT is a registered Danfoss trademark...
Page 42
0.1 s TRUE 27-41 Delay 10.0 s TRUE 27-6* Digital Inputs set- Uint1 27-42 Ramp Up Delay 2.0 s TRUE Terminal X66/1 [0] No set- 27-60 Digital Input operation TRUE Uint8 ® MI38C402 - VLT is a registered Danfoss trademark...
Page 43
Status 0 N/A TRUE r[25] Terminal X66/13 [0] No set- Advanced 27-66 Digital Input operation TRUE Uint8 Cascade Relay set- Uint1 27-7* Connections 27-95 Output [bin] 0 N/A TRUE Table 5.2 ® MI38C402 - VLT is a registered Danfoss trademark...
0 (s), Off Table 6.6 Master Drive Settings, 27-5* Alternate Settings An array parameter is used to configure the output of the master drive for the start signal of the follower drives. ® MI38C402 - VLT is a registered Danfoss trademark...
4-12 Motor Speed Low Limit [Hz] to enable sleep function (setting it to zero will disable the function). Set 27-21 Override Limit to wake up the application. After wake up the pump with the least running hours starts. ® MI38C402 - VLT is a registered Danfoss trademark...