[16-96 ] Prev.
9-27 Parameter Edit
Option:
[0]
*
[1]
9-28 Process Control
Option:
[0]
*
[1]
9-53 Profibus Warning Word
Option:
Read only
Bit:
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
9-63 Actual Baud Rate
Option:
Maintenance
Word
Function:
Parameters can be edited via Profibus, the standard RS485 in-
terface, or the LCP.
Disabled
Disables editing via Profibus.
Enabled
Enables editing via Profibus.
Function:
Process control (setting of Control Word, speed reference, and
process data) is possible via either Profibus or standard fieldbus
but not both simultaneously. Local control is always possible via
the LCP. Control via process control is possible via either termi-
nals or fieldbus depending on the settings in par. 8-50 to 8-56.
Disable
Disables process control via Profibus, and enables process con-
trol via standard fieldbus or Profibus Master class 2.
Enable cyclic master
Enables process control via Profibus Master Class 1, and disables
process control via standard fieldbus or Profibus Master class 2.
Function:
This parameter displays Profibus communication warnings.
Please refer to the
information.
Meaning:
Connection with DP-master is not
Not used
FDL (Field-bus Data link Layer) is not ok
Clear data command received
Actual value is not updated
Baudrate search
PROFIBUS ASIC is not transmitting
Initializing of PROFIBUS is not ok
Drive is tripped
Internal CAN error
Wrong configuration data from PLC
Wrong ID sent by PLC
Internal error occured
Not configured
Timeout active
Warning 34 active
Function:
This parameter displays the actual Profibus baud rate. The Pro-
fibus Master automatically sets the baud rate.
®
MG.20.O2.02 - VLT
is a registered Danfoss trademark
2. Parameter Description
Profibus Operating Instructions
2
for further
121