Initialisation To Default Settings - Danfoss VLT HVAC Drive FC 102 Operating Instructions Manual

315-1400 kw
Hide thumbs Also See for VLT HVAC Drive FC 102:
Table of Contents

Advertisement

How to Operate the Frequenc...

5.3.5 Initialisation to Default Settings

There are 2 ways to initialise the frequency converter to
default:
Recommended initialisation
Manual initialisation
Be aware that they have different impact according to the
following description.
Recommended initialisation (via 14-22 Operation Mode)
5
5
1.
Select 14-22 Operation Mode.
2.
Press [OK].
3.
Select [2] Initialisation (for NLCP select "2").
4.
Press [OK].
5.
Remove power to unit and wait for the display to
turn off.
6.
Reconnect power and the frequency converter is
reset. Note that first start-up takes a few more
seconds than normal.
7.
Press [Reset].
14-22 Operation Mode initialises all except:
14-50 RFI Filter.
8-30 Protocol.
8-31 Address.
8-32 Baud Rate.
8-35 Minimum Response Delay.
8-36 Max Response Delay.
8-37 Maximum Inter-Char Delay.
15-00 Operating hours to 15-05 Over Volt's.
15-20 Historic Log: Event to 15-22 Historic Log:
Time.
15-30 Alarm Log: Error Code to 15-32 Alarm Log:
Time.
NOTICE
Parameters selected in 0-25 My Personal Menu stay
present with default factory setting.
68
Operating Instructions
Manual initialisation
NOTICE
When carrying out manual initialisation, serial communi-
cation, RFI filter settings and fault log settings are reset.
Manual initialisation removes parameters selected in
0-25 My Personal Menu.
1.
2.
3.
4.
This parameter initialises all except:
15-00 Operating hours
15-03 Power Up's
15-04 Over Temp's
15-05 Over Volt's
Danfoss A/S © 08/2014 All rights reserved.
Disconnect from mains and wait until the display
turns off.
Press
2a
[Status] - [Main Menu] - [OK] at the
same time while powering up for the
LCP 102, graphical LCP.
2b
[Menu] while powering up for LCP 101,
numerical LCP.
Release the keys after 5 s.
The frequency converter is now programmed
according to default settings.
MG11F502