VLT
AQUA Drive Programming Guide
2.9. Main Menu - Communications and Options - Group
8
2.9.1. 8-** Comm. and Options
Parameter group for configuring communications and options.
2.9.2. 8-0* General Settings
General settings for communications and options.
8-01 Control Site
Option:
*
[0]
[1]
[2]
8-02 Control Word Source
Option:
[0]
[1]
[2]
[3]
[4]
[5]
[6]
Function:
Digital and ctrl. word Control by using both digital input and control word.
Digital only
Control by using digital inputs only.
Control word only
Control by using control word only.
The setting in this parameter overrides the settings in par. 8-50
to 8-56.
Function:
Select the source of the control word: one of two serial interfa-
ces or four installed options. During initial power-up, the fre-
quency converter automatically sets this parameter to
A
[3] if it detects a valid fieldbus option installed in slot A. If the
option is removed, the frequency converter detects a change in
the configuration, sets par. 8-02 back to default setting
Port
, and the frequency converter then trips. If an option is in-
stalled after initial power-up, the setting of par. 8-02 will not
change but the frequency converter will trip and display: Alarm
Option Changed
67
This parameter cannot be adjusted while the motor is running.
None
FC Port
FC USB
Option A
Option B
Option C0
Option C1
®
MG.20.O2.02 - VLT
is a registered Danfoss trademark
2. Parameter Description
.
2
Option
FC
107