OceanStor V5 Series
Parts Replacement
Figure 6-81 Closing the panel
Step 9 Confirm the replacement.
After the preceding procedure is complete, check services on the host for storage-
related errors. If any storage-related error is reported, contact Huawei technical
support.
----End
Follow-up Procedure
After the fan module is replaced, label it to facilitate subsequent operations.
6.4.2 Replacing a Fan Module (for 6800 V5/6800F V5)
This section describes how to replace a fan module.
Impact on the System
During the replacement of a fan module, the system's heat dissipation is affected
and the system temperature increases. If the controller reaches the self-protection
threshold (for example, if the CPU temperature reaches 97°C), the controller is
automatically powered off, degrading the system reliability.
Prerequisites
●
Issue 15 (2019-12-30)
The spare part is on hand.
Copyright © Huawei Technologies Co., Ltd.
6 Replacing CRUs
84