Replacing A Fan Module (High-Density Disk Enclosure) - Huawei OceanStor V5 Series Parts Replacement

Hide thumbs Also See for OceanStor V5 Series:
Table of Contents

Advertisement

OceanStor V5 Series
Parts Replacement
Figure 6-90 Running/Alarm indicator on a fan module
Step 8 Confirm the replacement.
After the preceding procedure is complete, check services on the host for storage-
related errors. If any storage-related error is reported, contact Huawei technical
support.
----End
Follow-up Procedure
After the fan module is replaced, label it to facilitate subsequent operations.

6.4.4 Replacing a Fan Module (High-Density Disk Enclosure)

This section describes how to replace a fan module.
Impact on the System
During the replacement of a fan module, the system's heat dissipation is affected
and the system temperature increases. If the temperature reaches the self-
protection threshold (for example, if the disk enclosure reaches 55°C), the disk
enclosure is automatically powered off, degrading the system reliability.
Prerequisites
Issue 15 (2019-12-30)
The spare part is on hand.
The fan module that you want to replace has been located.
You can locate a component in either of the following ways:
● Locating a component based on alarms in DeviceManager: On the Alarms and Events
page of DeviceManager, view the help information and determine the ID of the
component to be replaced. Then locate the component at your site based on its ID.
● Locating a component based on the status of its Running/Alarm indicator: For details
about the indicators on different components, see Indicator Introduction of each
Product Description specific to your product model and version.
component in the
Copyright © Huawei Technologies Co., Ltd.
6 Replacing CRUs
92

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Oceanstor v500r007

Table of Contents