Extend Telegram - Siemens SIMATIC ET 200pro Series Operating Instructions Manual

Low voltage converter for the distributed i/o system
Hide thumbs Also See for SIMATIC ET 200pro Series:
Table of Contents

Advertisement

Bit
Significance
8
1 = Speed deviation
within the tolerance
range
9
1 = Master control
requested
10
1 = Comparison
speed reached or
exceeded
11
0 = I, M or P limit
reached
12
1 = Holding brake
open
13
0 = Alarm, motor
overtemperature
14
1 = Motor rotates
clockwise
0 = Motor rotates
counterclockwise
15
0 = Alarm, inverter
thermal overload
7.4.1.2

Extend telegram

The converter interconnects the corresponding signals with the fieldbus interface. Generally,
the interconnections are protected so that they cannot be changed. With the appropriate
converter settings, these interconnections can be changed.
Extend telegram
The telegram can be extended, by "attaching" additional signals.
Procedure
Proceed as follows to extend a telegram:
1. Set p0922 = 999.
2. Interconnect additional PZD send words and PZD receive words with signals of your
choice via parameters r2050 and p2051.
You have extended the telegram.
Parameter
p0922
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257324B AE
Comments
Setpoint / actual value deviation within the tolerance range.
The automation system is requested to accept the inverter control.
Speed is greater than or equal to the corresponding maximum speed.
Comparison value for current, torque or power has been reached or
exceeded.
Signal to open and close a motor holding brake.
---
Internal inverter actual value > 0
Internal inverter actual value < 0
---
Description
PROFIdrive telegram selection
999:
Free telegram (message frame) configuration
7.4 Drive control via PROFIBUS and PROFINET
Advanced commissioning
Signal interconnec-
tion in the inverter
p2080[8] = r2197.7
p2080[9] = r0899.9
p2080[10] =
r2199.1
p2080[11] =
r1407.7
p2080[12] =
r0899.12
p2080[13] =
r2135.14
p2080[14] =
r2197.3
p2080[15] =
r0836.0 / r2135.15
97

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic et 200pro fc-2Simatic et 200pro fc-2 converter

Table of Contents