Parameters of the fault buffer and the fault history
Parameter
r0945
r0948
r0949
p0952
r2109
r2130
r2131
r2133
r2136
Extended settings for faults
Parameter
p2100[0 ... 19]
p2101[0 ... 19]
p2118[0 ... 19]
p2119[0 ... 19]
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257324B AE
Description
Fault code
Displays the numbers of the faults that have occurred
Fault time received in milliseconds
Displays the time in milliseconds when the fault occurred
Fault value
Displays additional information about the fault
Fault cases, counter
A fault case can contain one or several faults.
Number of fault cases that have occurred since the last acknowledgement. With
p0952 = 0 you delete the fault buffer and the fault history.
Fault time removed in milliseconds
Displays the time in milliseconds when the fault occurred
Fault time received in days
Displays the time in days when the fault occurred
Actual fault code
Displays the code of the oldest fault that is still active
Fault value for float values
Displays additional information about the fault that occurred for float values
Fault time removed in days
Displays the time in days when the fault was removed
Description
Setting the fault number for fault response
Selecting the faults for which the fault response should be changed.
You can modify the motor fault response for up to 20 different fault codes.
Setting, fault response
Setting the fault response for the selected fault
Setting the message number for the message type
Selection of the message for which the message type should be changed.
You can change up to 20 different faults into an alarm, or suppress faults:
Setting the message type
Setting the message type for the selected fault
1: Fault
2: Alarm
3: No message
Alarms, faults and system messages