Siemens SIMATIC ET 200pro Series Operating Instructions Manual page 139

Low voltage converter for the distributed i/o system
Hide thumbs Also See for SIMATIC ET 200pro Series:
Table of Contents

Advertisement

Parameter
p2291
p2292
Table 7- 27
Parameter
p2267
p2268
p2269
p2271
p2270
For further information refer to the function block diagrams 7950 ff of the List Manual.
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257324B AE
Remark
CO: Technology maximum limiting (factory setting: 100 %)
CO: Technology minimum limiting (factory setting: 0 %)
Manipulating the actual value of the technology controller
Remark
Technology controller upper limit actual value (factory setting: 100 %)
Technology controller lower limit actual value (factory setting: -100 %)
Technology controller gain actual value (factory setting: 100 %)
Technology controller actual value inversion (sensor type)
0:
No inversion
1:
Inversion actual value signal
If the actual value decreases with increasing motor speed, then p2271 must
be set = 1.
Technology controller actual value function
0:
No function
1:
2:
x
2
3:
x
3
Advanced commissioning
7.10 PID technology controller
139