Advanced commissioning
7.19 PROFIenergy profile for PROFINET
To do so, you must set one of the following settings:
● p5611.1 = 1: With the transition to the energy-saving mode, the inverter issues an OFF1
command and enters the start-inhibit state (S1).
● p5611.1 = 0: You can use p5614 to interconnect a signal source that switches the inverter
off and places it in the start inhibited state (S1).
If the control sends the command "End_Pause" or "Start_Pause" with a pause time of 0, then
the inverter does not restart, even if the appropriate enable signals are still set.
An OFF1/on command is required in order that the inverter restarts.
PROFIenergy measured values
PROFIenergy
Measured value
ID
Name
34
Active power
166
Power factor
200
Active energy import
7.19.3

Control commands and status queries

PROFIenergy control commands
● Start_Pause
Dependent on the pause duration, switches into the energy-saving mode.
– For p5611.2 = 0, from operating states S1 (switching on inhibited) or S2 (ready to
– For p5611.2 = 1, also from operating states S3 (ready) or S4 (operation).
● Start_Pause_with_time_response
Dependent on the pause duration switches into the energy-saving mode and also
specifies the transition times in the command response.
– For p5611.2 = 0, from operating states S1 (switching on inhibited) or S2 (ready to
– For p5611.2 = 1, also from operating states S3 (ready) or S4 (operation).
● End_Pause
Switches from energy-saving mode to the operating state.
Cancels the switching from the operating state to the energy-saving mode.
176
Accuracy
Unit
Domain
Class
1
12
W
1
12
1
2
11
Wh
switch on)
switch on)
SINAMICS source parameters
Number
Name
r0032
Active power smoothed
r0038
Smoothed power factor
r0039[1]
Energy accepted
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257324B AE
Range of
values
r2004
0 ... 1
-
SIMATIC ET 200pro FC-2 converter