8.3
Saving settings on an operator panel
Precondition
When the power supply is switched on, you
can transfer the inverter settings to the IOP
or vice versa, transfer the IOP data to the
inverter.
Inverter → IOP
Procedure
To back up the settings on the IOP, proceed as follows:
1. Connect the operator panel to the inverter.
2. Start data transfer in the menu "UP/DOWNLOAD" -
"Drive to panel".
You have backed up the settings to the IOP.
IOP → inverter
Procedure
To transfer the settings to the inverter, proceed as follows:
1. Connect the operator panel to the inverter.
2. Start data transfer in the menu "UP/DOWNLOAD" -
"Panel to drive".
3. Switch off the inverter supply voltage.
4. Wait until all LEDs on the inverter go dark. Now
switch on the inverter supply voltage again. Your
settings only become effective after this power-on
reset.
You have transferred the settings to the inverter.
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257324B AE
Backing up data and series commissioning
8.3 Saving settings on an operator panel
187