Alarms, faults and system messages
10.6 List of alarms and faults
Number
Cause
A01698
Commissioning mode active for
safety functions
A01699
Switch-off signal path test required
A01910
Fieldbus SS setpoint timeout
F01910
A01920
PROFIBUS: Cyclic connection
interrupt
A03520
Temperature sensor fault
A05000
Power Module overtemperature
A05001
A05002
A05004
A05006
F06310
Supply voltage (p0210) incorrectly
set
F07011
Motor overtemperature
A07012
I2t Motor Module overtemperature
A07015
Motor temperature sensor alarm
F07016
Motor temperature sensor fault
F07086
Switching over units: Parameter
F07088
limit violation
F07320
Automatic restart aborted
A07321
Automatic restart active
F07330
Search current measured too low
230
Remedy
This message is withdrawn after the Safety commissioning has ended.
After the next time that the "STO" function is deselected, the message is
withdrawn and the monitoring time is reset.
The alarm is generated when p2040 ≠ 0 ms and one of the following
causes is present:
The bus connection is interrupted
Communications error (CRC, parity bit, logical error)
An excessively low value for the fieldbus monitoring time (p2040)
Explanation: The cyclic connection to PROFIBUS master is interrupted.
Establish the PROFIBUS connection and activate the PROFIBUS master
with cyclic operation.
Check that the sensor is connected correctly.
Check the following:
- Is the ambient temperature within the defined limit values?
- Are the load conditions and duty cycle configured accordingly?
- Has the cooling failed?
Check the set supply voltage and if required change (p0210).
Check the line voltage.
Reduce the motor load.
Check ambient temperature.
Check the wiring and connection of the sensor.
Check and if necessary reduce the motor load.
Check the motor's ambient temperature.
Check thermal time constant p0611.
Check overtemperature fault threshold p0605.
Check that the sensor is connected correctly.
Check the parameter assignment (p0601).
Make sure that the sensor is connected correctly.
Check the parameterization (p0601).
Deactivate the motor temperature sensor fault evaluation (p0607 = 0).
Check the adapted parameter values and if required correct.
Increase the number of restart attempts (p1211). The actual number of
start attempts is shown in r1214.
Increase the wait time in p1212 and/or monitoring time in p1213.
Connect an ON command (p0840).
Increase the monitoring time of the power unit or switch off (p0857).
Reduce the wait time for resetting the fault counter p1213[1] so that fewer
faults are registered in the time interval.
Explanation: The automatic restart (AR) is active. During voltage recovery
and/or when remedying the causes of pending faults, the drive is auto-
matically switched back on.
Increase search current (p1202), check motor connection.
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257324B AE