Alarms, faults and system messages
10.6 List of alarms and faults
Number
Cause
F07902
Motor stalled
A07903
Motor speed deviation
F07909
Internal voltage protection: Deacti-
vation only active after POWER
ON
A07910
Motor overtemperature
A07920
Torque/speed too low
A07921
Torque/speed too high
A07922
Torque/speed out of tolerance
F07923
Torque/speed too low
F07924
Torque/speed too high
A07927
DC braking active
F7966
Check commutation angle
F7969
Pole position identification incorrect An error has occurred during the pole position identification.
A07980
Rotary measurement activated
A07981
No enabling for rotary measure-
ment
A07991
Motor identification activated
F08501
Setpoint timeout
F08502
Monitoring time, sign-of-life expired •
A08511
Receive configuration data not
valid
A08526
No cyclic connection
A08565
Consistency error affecting adjust-
able parameters
232
Remedy
Check whether the motor data has been set correctly and perform a mo-
tor identification.
Check the current limits (p0640, r0067, r0289). If the current limits are too
low, the drive cannot be magnetized.
Check whether motor cables are disconnected during operation.
Increase p2163 and/or p2166.
Increase the torque, current and power limits.
The inverter has activated the "Internal voltage protection" function"
(p1231 = 3). Deactivation of the internal voltage protection (p1231 ≠ 3)
only becomes active after POWER ON.
Check the motor load.
Check the motor's ambient temperature.
Check the KTY84 or Pt1000 sensor.
Check the overtemperatures of the thermal model (p0626 ... p0628).
The torque deviates from the torque/speed envelope curve.
Check the connection between the motor and the load.
Adapt the parameterization corresponding to the load.
Check the connection between the motor and the load.
Adapt the parameterization corresponding to the load.
Not required
Carry out pole position identification.
Check the following:
Motor connection
Motor data
Not required
Acknowledge pending faults.
Establish missing enables (see r00002, r0046).
Switch on the motor and identify the motor data.
Check the bus connection.
Set the controller into the RUN mode.
If the fault occurs repeatedly, check the monitoring time set p2044.
Check the bus connection.
Check the bus configuration
Activate the controller with cyclic operation.
Check the parameters "Name of Station" and "IP of Station" (r61000,
r61001).
Check the following:
IP address, subnet mask or default gateway is not correct.
IP address or station name used twice in the network.
Station name contains invalid characters.
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257324B AE