Siemens SIMATIC ET 200pro Series Operating Instructions Manual page 102

Low voltage converter for the distributed i/o system
Hide thumbs Also See for SIMATIC ET 200pro Series:
Table of Contents

Advertisement

Advanced commissioning
7.4 Drive control via PROFIBUS and PROFINET
Error
Meaning
value 1
11 hex
Request cannot be executed due to the operating state (access is not possible for temporary reasons that are
not specified)
14 hex
Inadmissible value (change request with a value that is within the limits but which is illegal for other permanent
reasons, i.e. a parameter with defined individual values)
15 hex
Response too long (the length of the actual response exceeds the maximum transfer length)
16 hex
Illegal parameter address (illegal or unsupported value for attribute, number of elements, parameter number,
subindex or a combination of these)
17 hex
Illegal format (change request for an illegal or unsupported format)
18 hex
Number of values not consistent (number of values of the parameter data to not match the number of elements
in the parameter address)
19 hex
Drive object does not exist (access to a drive object that does not exist)
20 hex
Parameter text cannot be changed
21 hex
Service is not supported (illegal or not support request ID).
6B hex
A change request for a controller that has been enabled is not possible. (The inverter rejects the change re-
quest because the motor is switched on. Please observe the "Can be changed" parameter attribute (C1, C2, U,
T) in the List Manual.
Manuals for your inverter (Page 262))
6C hex
Unknown unit.
6E hex
Change request is only possible when the motor is being commissioned (p0010 = 3).
6F hex
Change request is only possible when the power unit is being commissioned (p0010 = 2).
70 hex
Change request is only possible for quick commissioning (basic commissioning) (p0010 = 1).
71 hex
Change request is only possible if the inverter is ready (p0010 = 0).
72 hex
Change request is only possible for a parameter reset (restore to factory setting) (p0010 = 30).
73 hex
Change request possible only during commissioning of the safety functions (p0010 = 95).
74 hex
Change request is only possible when a technological application/unit is being commissioned (p0010 = 5).
75 hex
Change request is only possible in a commissioning state (p0010 ≠ 0).
76 hex
Change request is not possible for internal reasons (p0010 = 29).
77 hex
Change request is not possible during download.
81 hex
Change request is not possible during download.
82 hex
Accepting the master control is inhibited via BI: p0806.
83 hex
Desired interconnection is not possible (the connector output does not supply a float value although the con-
nector input requires a float value)
84 hex
Inverter does not accept a change request (inverter is busy with internal calculations. See parameter r3996 in
the inverter List Manual.
Manuals for your inverter (Page 262))
85 hex
No access methods defined.
86 hex
Write access only during commissioning of the data records (p0010 = 15) (operating status of the inverter pre-
vents a parameter change.)
87 hex
Know-how protection active, access locked
C8 hex
Change request below the currently valid limit (change request to a value that lies within the "absolute" limits,
but is however below the currently valid lower limit)
C9 hex
Change request above the currently valid limit (example: a parameter value is too large for the inverter power)
CC hex
Change request not permitted (change is not permitted as the access code is not available)
102
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257324B AE
SIMATIC ET 200pro FC-2 converter