Diagnostics alarm with DS0 / DS1
1)
2)
3)
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257324B AE
Alarm specifier
1: Fault is active and the slot is not OK
2: Fault is resolved and the slot is OK
3: Fault is resolved and the slot is not OK
Channel fault present
0: No fault is active
1: Fault is active
Internal fault
0: No fault is active
1: Fault is active
Alarms, faults and system messages
10.2 Diagnostics through fieldbus
4)
Module fault
0: No fault is active
1: Fault is active
5)
Channel information present
1: DS1 exists
6)
Type of class module = 0011
(distributed)
219