Installation
4.1 Prerequisites and maximum expansion
4.1
Prerequisites and maximum expansion
Danger to life from spread of fire in the event of contact with hot surfaces
The inverter housing can reach an operating temperature that may cause a fire.
• Store easily inflammable materials at a sufficient distance from the inverter.
Maximum size
The width of an ET 200pro is limited mechanically and electrically.
Table 4- 1
Features
Number of mod-
ules
Width
Number of invert-
ers
Table 4- 2
ET 200pro features
Load capacity of the electronics supply 1L+
Load capacity of the load voltage supply 2L+
Current carrying capacity of the power supply
4.2
Mounting the racks
The frequency converter is mounted on the wide rack. The following versions are possible:
● Rack, wide
● Rack, compact-wide
32
WARNING
Mechanical limits
Rule
≤ 16
≤ 1 m (without rack)
≤ 5
Electrical limits
Inverter features
Power consumption at 1L+
Power consumption at 2L+
Power consumption at the
power supply
Rule
≤ 5 A
≤ 0.8 A per inverter
≤ 10 A
The load caused by the frequency inverter
is negligible.
≤ 25 A
The inverter's power consumption depends
on the connected motor.
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257324B AE
SIMATIC ET 200pro FC-2 converter