Stable Light Threshold Adjustment - Omron F3SG-SRB Series User Manual

Hide thumbs Also See for F3SG-SRB Series:
Table of Contents

Advertisement

Setting with SD Manager 3

4-3-5-2. Stable Light Threshold Adjustment

First, carry out 4-3-1. Preparing to Change Settings.
Next, on the Top page, click the icon below.
The setting screen below is displayed.
No.
Function name
1
Stable light threshold
For more information on stable light threshold adjustment, refer to 2-24. Stable Light Threshold Adjustment.
When the stable light threshold value is changed, the following threshold values of the output information are also
changed.
· Auxiliary Output: Stable-state information and Light level diagnosis information (upper limit)
· Area Beam Indicator: Stable-state information and Light level diagnosis information (upper limit)
· IO-Link Process Data: Light level diagnosis information (upper limit)
When changing the settings is complete, confirm the settings and write the configuration to the F3SG-SR.
To enable the written configuration, refer to 4-2-7-3. Writing Configuration into Intelligent Tap.
When connecting the Intelligent Tap to a F3SG-SR and trying to return the F3SG-SR to [Detecting], follow step 4 of
4-1-3-2. Connection Procedure When Using USB Connector to restart the F3SG-SR and Intelligent Tap, or click the
[Monitor]
F3SG-SR
218
User's Manual
Set stable light threshold. Set the parameter by moving
the pointer of the bar.
button.
Description
Configurable value or
Initial value
numerical range
170%
100 to 300%