The values of T1
and T1
min
Time t2 [ s ] for a workpiece to pass the F3SG-SR's detection zone after passing the muting sensor A1
is:
t2 = d2 / VEquation (3)d2 [ m ] : Distance between muting sensor A1 and F3SG-SR
V [ m/s ] : Approach speed of a workpiece
Time t2 in Equation (3) must satisfy following condition:
t2 < T5Equation (4)T5: Exit-only muting delay time
The value of T5 can be changed by the SD Manager 3.
Sensors must be installed so that person's passing should not cause the MUTING state.
Also, the muting sensors and F3SG-SR must be installed so that MUTING state caused by a
workpiece should be ended before the next workpiece arrives at the first muting sensor.
Hazardous zone
A1 B1
Workpiece
Moving direction
 Timing chart
ON
Muting input A
(Muting sensor A1)
OFF
ON
Muting input B
(Muting sensor B1)
OFF
Enabled
MUTING state
Disabled
ON
ABI indicator
OFF
Unblocked
Beam state
Blocked
ON
OSSD
OFF
* 102 ms max. when the
Intelligent Tap is connected
to the F3SG-SR.
can be changed by the SD Manager 3.
max
F3SG-SR
Workpiece
T3 (0.1 s) max.
T1min to T1max
T2 max.
T1max
80 ms max. *
Green blinking
Orange blinking
T1min: Muting input time limit value (minimum)
T1max: Muting input time limit value (maximum)
T2: Muting time limit
T3: Maximum allowable muting signal interruption
T4: Muting end wait time
T5: Exit-only muting delay time
System Operation and Functions
Hazardous zone
A1 B1
F3SG-SR
Workpiece
Workpiece
Moving direction
T3(1 s) max.
T5 max.
T4 (1 s)
E
F3SG-SR
77