System Operation and Functions
2-14-3. Override upon Startup
You can enable the OVERRIDE state by entering a special sequence when the power is turned on.
This function is dedicated to Exit-Only Muting mode.
Under the Standard Muting mode or the Position Detection Muting mode, a workpiece can be ejected using the Override
function under the normal operation as any of muting inputs always turns on even if the power is restarted while muting
failed.
Override start conditions
When all of the following conditions are satisfied, the OVERRIDE state is enabled. The OVERRIDE
state can be achieved even when there is a muting error.
1. The F3SG-SR is blocked
2. An input signal of a special sequence is entered three times to the RESET line within 3 to 6 s after
power-on. The signal must be entered within a range from 0.2 s to the override input time limit T1
(initial value: 1 s). (See the timing chart below.)
Override end conditions
When any one of the following conditions is satisfied, the OVERRIDE state is released.
1. A period of 600 s (configurable) passes in the OVERRIDE state
2. The F3SG-SR is unblocked
3. The following signal to cancel the OVERRIDE state is entered:
• When the external device monitoring function is enabled, the RESET line is turned ON. (PNP:
Connected to Vs-3 V~Vs; NPN: Connected to 0 V~3 V)
• When the external device monitoring function is disabled, the RESET line is turned OFF.
The OVERRIDE state can be also released when the F3SG-SR enters the LOCKOUT state.
Timing chart
Power
RESET
OVERRIDE state
Beam state
OSSD
2-14-4. Setting with Intelligent Tap
The user cannot make any changes to this function by the DIP Switch.
F3SG-SR
88
User's Manual
ON
OFF
ON
T1 T1 T1 T1 T1 T1
OFF
1 s max.
Enabled
Disabled
Unblocked
Blocked
ON
OFF
3 to 6 s
T2 max.
1 s max.
T1: Override input time limit
T2: Override time limit