Omron F3SG-SRB Series User Manual page 92

Hide thumbs Also See for F3SG-SRB Series:
Table of Contents

Advertisement

System Operation and Functions
 End conditions
If either of the following conditions is satisfied, the MUTING state is released.
• The muting input A or B turns OFF for the maximum allowable muting signal interruption of T3 (at
least 0.1 s: configurable) or longer.
• The duration of the MUTING state exceeds the muting time limit of T2 (at least 60 s: configurable).
The MUTING state is also released when the F3SG-SR enters the LOCKOUT state.
 Timing chart
Muting input A
Muting input B
MUTING state
ABI indicator
Beam state
OSSD
 Factory default setting
Variable
T
1min
T
1max
T
2
T
3
F3SG-SR
64
User's Manual
ON
OFF
T1min to T1max
ON
OFF
80 ms max. *
Enabled
Disabled
Orange
blinking
ON
OFF
Unblocked
Blocked
ON
OFF
* 102 ms max. when the
Intelligent Tap is connected
to the F3SG-SR.
Variable name
Muting input time limit value
(minimum)
Muting input time limit value
(maximum)
Muting time limit
Maximum allowable muting
signal interruption
T3 max.
T3 max.
T2 max.
Green blinking
T1min: Muting input time limit value (minimum)
T1max: Muting input time limit value (maximum)
T2: Muting time limit
T3: Maximum allowable muting signal interruption
Value
0.1 s
Minimum time difference between muting inputs A and B.
If the time difference between muting inputs A and B is smaller
than this value, a muting sequence error occurs.
4 s
Maximum time difference between muting inputs A and B.
If the time difference between muting inputs A and B is larger
than this value, a muting sequence error occurs.
60 s
The duration time of the Muting function. The MUTING state is
cancelled if it continues for longer than this time limit.
0.1 s
Maximum duration of a signal interruption allowed in muting
inputs A and B.
Orange blinking
Description

Advertisement

Table of Contents
loading

This manual is also suitable for:

F3sg-sr seriesF3sg-sra series

Table of Contents