System Operation and Functions
 End conditions
If any of the following condition is satisfied, the MUTING state is released.
• When a workpiece passes the muting sensor A or B and the exit-only muting delay time (4 s: Can
be changed) passes.
• When a workpiece passes the F3SG-SR's detection zone and the muting end wait time (1 s:
configurable) passes.
• The duration of the MUTING state exceeds the muting time limit (60 s: configurable).
The MUTING state is also released when the F3SG-SR enters the LOCKOUT state.
 Timing chart
Muting input A
(Muting sensor A1)
Muting input B
(Muting sensor B1)
MUTING state
ABI indicator
Beam state
OSSD
Note. This timing chart shows the case in which the MUTING state was released under the condition of T4 (1 s).
 Factory default setting
Variable
T1min
T1max
T2
T3
T4
T5
The MUTING state is also released when the F3SG-SR enters the LOCKOUT state.
F3SG-SR
74
User's Manual
T3 (0.1 s) max.
ON
OFF
T1min to T1max
ON
OFF
80 ms max. *
Enabled
Disabled
Orange
blinking
ON
OFF
Unblocked
Blocked
ON
OFF
* 102 ms max. when the
Intelligent Tap is connected
to the F3SG-SR.
Variable name
Muting input time limit value
0.1 s
(minimum)
Muting input time limit value
4 s
(maximum)
Muting time limit
60 s
Maximum allowable muting
0.1 s
signal interruption
Muting end wait time
1 s
Exit-only muting delay time
4 s
T3 (0.1 s) max.
T2 max.
T3 (0.1s) max.
T5 max.
Green blinking
T1min: Muting input time limit value (minimum)
T1max: Muting input time limit value (maximum)
T2: Muting time limit
T3: Maximum allowable muting signal interruption
T4: Muting end wait time
T5: Exit-only muting delay time
Value
Minimum time difference between muting inputs A and B.
If the time difference between muting inputs A and B is smaller
than this value, a muting sequence error occurs.
Maximum time difference between muting inputs A and B.
If the time difference between muting inputs A and B is larger
than this value, a muting sequence error occurs.
The duration time of the Muting function. The MUTING state is
cancelled if it continues for longer than this time limit.
Maximum duration of a signal interruption allowed in muting
inputs A and B.
Time difference from when the F3SG-SR is unblocked until the
MUTING state is cancelled.
Time difference from when the signal of Muting input A or B is
turned OFF until the MUTING state is cancelled.
T4 (1 s)
Description