SENSORS AND MODULES CHECKS

Each device has an associated instruction leaflet showing the correct interconnections for various applications.
Survey the site to check and ensure devices are installed in the location identified on 'As fitted system wiring
drawings' and according to the instructions.
The Notifier INSPIRE E10/E15 Control Panel support supports devices incorporating internal isolators, providing
the bases with the additional positive leg loop wiring connectors (type B501 AP) are used. However, devices will
work satisfactorily when used with bases without these additional wiring connectors except the internal isolator,
when fitted, cannot be operated.
The Notifier INSPIRE E10/E15 Control panel Dual Loop module Opal (HOP-433-100) has the capacity to
allows connection of up to 318 loop OPAL devices per analogue loop, consisting of up to 159 detectors and 159
modules.
A loop can operate in legacy CLIP mode which can be activated through a dedicated license. The capacity of a
CLIP loop is limited to 99 detectors + 99 other devices