Stabilizer/Outrigger Bracket Positions - EMC Connectrix EC-1200 Planning Manual

2 gb/s enterprise storage network system
Table of Contents

Advertisement

EC-1200 Connectrix Cabinet
1

Stabilizer/Outrigger Bracket Positions

Figure 1-11
Figure 1-11 shows the front of the cabinet. Installation of the rear
brackets is similar.
CAUTION
!
EMC recommends keeping the Connectrix Stabilizer / Outrigger
brackets , P/N 100-605-014, on the EC-1200 cabinet at all times.
When the cabinet is positioned such that it is not immediately
adjacent (within 2 inches) to another equipment cabinet, the
stabilizer bracket outriggers must be positioned in their outermost
position. If the cabinet is positioned within 2 inches of another
equipment cabinet, the outrigger brackets can be positioned in
their innermost position. Any side of the EC-1200 cabinet that is
not within 2 inches of another equipment cabinet should have that
side's outriggers positioned in the outermost position. These rules
apply not only for initial installation, but also if the EC-1200 switch
and/or director configuration is altered at a later date.
1-16
Connectrix v6.02 Planning Guide