Ed-140M Director - EMC Connectrix EC-1200 Planning Manual

2 gb/s enterprise storage network system
Table of Contents

Advertisement

ED-140M Director

Physical
Characteristics
Power
Requirements
Operating
Environment
Dimensions
Height: 20.9 in (53.1 cm)
Width: 17.5 in (44.5 cm)
Depth: 24.2 in (61.5 cm)
Weight
167.0 lbs (75.9 kg)
Airflow Clearance in
Rack
Shock and Vibration
60 Gs for 10 milliseconds without nonrecoverable errors
Tolerance
Acoustical Noise
70 dB "A" scale
Heat Dissipation
35 UPM cards: 842W (2,873 BTU/hr)
Input voltage
200 to 264 VAC, 47 to 73 Hz
Current
4.66 A at 180 VAC
Power is provided by the EC-1200 cabinet; refer to Power
Requirements on page F-2 for electrical service requirements
of the EC-1200.
°
Temperature
40
Relative Humidity
8% to 80%
°
Maximum Wet-Bulb
81
Temperature
Maximum Altitude
10,000 ft (3,048 m)
Inclination
10° maximum
Top and bottom: None
Front and rear: 3.0 in (7.6 cm)
Sides: 2.0 in (5.1 cm)
°
°
°
F to 104
F (4
C to 40
C)
°
F (27
C)
Specifications
Specifications
F-9
F