Maintenance And Troubleshooting; General Maintenance Guidelines; Specific Maintenance Guidelines - Siemens IONPURE VNX50HH-2 Operation & Maintenance Manual

Table of Contents

Advertisement

®
IONPURE

6. MAINTENANCE AND TROUBLESHOOTING

The cleaning chemical volumes and flows detailed in this section are for a single VNX module. Multiply
chemical volumes by number of modules in system
This section also lists possible problems and troubleshooting procedures for the VNX module. All
operators and personnel involved with the module should read and become familiar with all maintenance
and troubleshooting procedures.

6.1. General Maintenance Guidelines

Operating Data Log Sheet
VNX system log sheets should be filled out daily to provide early detection of problems that could
jeopardize the warranty and potentially damage the module. A typical log sheet is included at the
end of the troubleshooting in Section 7. Because instrumentation may vary depending on the type
of system the module is installed into, this log sheet may not apply to your particular system. The
system manual should contain log sheets more appropriate for your particular system. However,
the items in bold must be filled out to maintain module warranty.
Periodic Maintenance
Perform the following tests at least once every six months. Check the Troubleshooting portion in
Section 7 for any recommendations that are not listed below.

6.2. Specific Maintenance Guidelines

Periodically, the VNX module may need cleaning or sanitization. Cleaning the module removes
scale and resin/membrane foulants.
Before starting any cleaning or sanitization procedure, see subsection 6.7
for recommended cleaning solutions
Do not run a cleaning or sanitizing solution through the system with DC
power to the VNX module. Make sure the DC power is off before cleaning.
Page 18
VNX50HH-2 CEDI Modules
The following section details the maintenance procedures for the VNX module. It
contains general maintenance information and specific maintenance information
for cleaning and sanitizing the modules.
Check for any water leakage from the module. If leakage is observed,
see the Troubleshooting subsection for possible solutions.
Periodically tighten all electrical connections.
IP-MAN-VNX50HH2

Advertisement

Table of Contents
loading

Table of Contents