Data Point Display (Visibility); Troubleshooting; Customized Texts - Siemens Synco RMZ792 Series Basic Documentation

Bus operator unit
Hide thumbs Also See for Synco RMZ792 Series:
Table of Contents

Advertisement

Possible cases
Siemens
Building Technologies
3.3

Data point display (visibility)

The bus operator unit's interface only displays data points for the Synco 700 control
units needed for the current device configuration.
In the case of other devices (e.g. RX.. room controller), the bus operator unit displays
all data points regardless of configuration. As a result, data points may not reflect real
values or setting values may not trigger any action, as the current device's configuration
may not support them or may be ineffective.
3.4

Troubleshooting

Fault / Fault status message
Caution!
Device version not supported
Caution!
Device not responding
Data does not show real value (e.g.
room temperature 655.3 °C).
Setting has no effect.
3.5

Customized texts

Customized device texts are taken over, i.e. the bus operator unit display is identical
to that on the local operator unit (RMZ790/791). The bus operator unit reads the
customized text from the corresponding device. The factory-set default text is displayed
until the customized text is received.
Bus operator unit RMZ792 Series B
3 Device operation
Cause / Solution
• The device list for the bus operator
unit and the software version of the
target device may not match, or the
device is not supported.
• Determine which versions of bus
operator unit and target device are
compatible. See Valid Version Set,
J3100.
• Exchange bus operator unit or target
device.
• No communication with target device.
• Is the device operating?
• Is the device connected to the KNX
bus?
• Was the device address changed?
The data point in the current
configuration is useless (device does not
support data point visibility).
The data point in the current
configuration is useless (device does not
support data point visibility).