3.4.6 The Data Field
The structure of data blocks depends on the type of telegram. There are 3 telegram types, and the type applies for both
control telegrams (master⇒follower) and response telegrams (follower⇒master).
3
3
The 3 types of telegram are:
Process block (PCD)
The PCD is made up of a data block of 4 bytes (2 words) and contains:
Control word and reference value (from master to follower)
Status word and present output frequency (from follower to master)
STX
LGE
Illustration 3.7 Process Block
Parameter block
The parameter block is used to transfer parameters between master and follower. The data block is made up of 12 bytes (6
words) and also contains the process block.
STX
LGE
Illustration 3.8 Parameter Block
Text block
The text block is used to read texts via the data block.
STX
LGE
Illustration 3.9 Text Block

3.4.7 The PKE Field

The PKE field contains 2 subfields: Parameter command
and response (AK) and Parameter number (PNU):
20
VLT
ADR
PCD1
ADR
PKE
IND
ADR
PKE
IND
Ch1
®
DriveMotor FCP 106 and FCM 106 Programming Guide
PWE
PWE
high
low
Ch2
Chn
AK
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Illustration 3.10 PKE Field
MG03N102 - Rev. 2013-12-02
PCD2
PCD1
PCD2
PCD1
PCD2
PKE
IND
PWE
high
PNU
BCC
BCC
BCC
PWE