2.6 Restoring Default Settings

Select initialisation mode according to the requirement for
retaining parameter settings.
Recommended initialisation (via
parameter 14-22 Operation Mode).
Use this method to perform initialisation without resetting
communication settings.
1.
Select parameter 14-22 Operation Mode.
2.
Press [OK].
3.
Select Initialisation and Press [OK].
4.
Cut off the mains supply and wait until the
display turns off.
5.
Reconnect the mains supply
6.
The frequency converter is now reset, with the
exception of the following parameters:
8-30 Protocol
parameter 8-31 Address
parameter 8-32 Baud Rate
parameter 8-33 Parity / Stop Bits
parameter 8-35 Minimum Response Delay
parameter 8-36 Maximum Response Delay
parameter 8-70 BACnet Device Instance
parameter 8-72 MS/TP Max Masters
parameter 8-73 MS/TP Max Info Frames
parameter 8-74 "I am" Service
parameter 8-75 Intialisation Password
parameter 15-00 Operating hours to
parameter 15-05 Over Volt's
parameter 15-03 Power Up's
parameter 15-04 Over Temp's
parameter 15-05 Over Volt's
parameter 15-30 Alarm Log: Error Code
15-4* Drive identification parameters
parameter 1-06 Clockwise Direction
2-finger initialisation
Use this method to perform initialisation, including reset of
communication settings.
1.
Power off the frequency converter.
2.
Press [OK] and [Menu] simultaneously.
3.
Power up the frequency converter while still
pressing the keys above for 10 s.
4.
The frequency converter is now reset, with the
exception of the following parameters:
®
VLT
DriveMotor FCP 106 and FCM 106 Programming Guide
The alarm AL80 appears as confirmation that parameters
are initialised. Press [Reset].
MG03N102 - Rev. 2013-12-02
parameter 15-00 Operating hours
parameter 15-03 Power Up's
parameter 15-04 Over Temp's
parameter 15-05 Over Volt's
15-4* Drive identification parameters