Parameters
4.10.3 14-2* Trip Reset
14-20 Reset Mode
Option:
Function:
NOTICE
Automatic reset is also active
for resetting safe stop function.
Select the reset function after
tripping. Once reset, the frequency
converter can be restarted.
[0]
Manual reset
Select [0] Manual reset, to perform a
*
reset via [Reset] or via the digital
inputs.
[1]
Automatic reset x 1
Select [1]-[12] Automatic reset x 1...
x20 to perform between 1 and 20
automatic resets after tripping.
[2]
Automatic reset x 2
[3]
Automatic reset x 3
[4]
Automatic reset x 4
[5]
Automatic reset x 5
[6]
Automatic reset x 6
[7]
Automatic reset x 7
[8]
Automatic reset x 8
[9]
Automatic reset x 9
[10] Automatic reset x 10
[11] Automatic reset x 15
[12] Automatic reset x 20
[13] Infinite auto reset
Select [13] Infinite Automatic Reset for
continuous resetting after tripping.
14-21 Automatic Restart Time
Range:
Function:
10 s
[0 - 600
Enter the time interval from trip to start of the
*
s]
automatic reset function. This parameter is
active when parameter 14-20 Reset Mode is set
to [1] - [13] Automatic reset.
14-22 Operation Mode
Option:
Function:
Select [2] Initialisation to reset all parameter
values to default.
[0]
Normal
Select [0] Normal operation for normal
operation
operation of the frequency converter with the
*
motor in the selected application.
[2]
Initiali-
Select [2] Initialisation to reset all parameter
sation
values to default settings, except for
parameter 15-03 Power Up's,
parameter 15-04 Over Temp's and
parameter 15-05 Over Volt's. The frequency
converter is reset during the next power-up.
®
VLT
DriveMotor FCP 106 and FCM 106 Programming Guide
14-22 Operation Mode
Option:
14-27 Action At Inverter Fault
Option:
[0]
Trip
[1]
Warning
*
4.10.4 14-4* Energy Optimising
Parameters for adjusting the energy optimisation level in
both Variable Torque (VT) and Automatic Energy Optimi-
sation (AEO) mode.
Automatic Energy Optimisation is only active if
parameter 1-03 Torque Characteristics, is set for [3] Auto
Energy Optim.
14-40 VT Level
Range:
90 %
*
90%
*
14-41 AEO Minimum Magnetisation
Range:
66 %
*
66%
*
4.10.5 14-5* Environment
These parameters help the frequency converter to operate
under special environmental conditions.
14-51 DC-Link Voltage Compensation
Option:
[0]
[1]
*
MG03N102 - Rev. 2013-12-02
Function:
Parameter 14-22 Operation Mode also reverts to
the default setting [0] Normal operation.
Function:
Select how the frequency converter should react
at inverter fault. Action At Inverter Fault
Function:
NOTICE
[40 - 90 %]
This parameter cannot be adjusted
while the motor is running.
Enter the level of motor magnetisation at
low speed. Selection of a low value reduces
energy loss in the motor, but also reduces
load capability.
[40-90%]
Function:
[40 - 75 %] Enter the minimum allowable magnetisation
for AEO. Selection of a low value reduces
energy loss in the motor, but can also
reduce resistance to sudden load changes.
[40-75%]
Function:
Off
Disables DC Link Compensation.
On
Enables DC Link Compensation.
4
4
77