Parameters
4.12.5 16-5* Ref. & Feedb.
16-50 External Reference
Range:
Function:
0 %
[-200 - 200 %] View the total reference, the sum of
*
digital, analog, preset, bus and freeze
references.
16-52 Feedback[Unit]
Range:
0
[-4999 - 4999
ProcessCtrlUnit
ProcessCtrlUnit]
*
4.12.6 16-6* Inputs and Outputs
16-60 Digital Input
Range:
Function:
0
[0 -
View actual state of the digital inputs 18, 19, 27
*
65535 ]
and 29.
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6~15
Table 4.9 Bits Definition
16-61 Terminal 53 Setting
Option:
Function:
View the setting of input terminal 53.
Current = 0; Voltage = 1.
[0]
Current mode
*
[1]
Voltage mode
16-62 Analog Input AI53
Range:
Function:
1
[0 - 20 ]
View the actual value at input 53.
*
16-63 Terminal 54 Setting
Option:
Function:
View the setting of input terminal 54.
Current = 0; Voltage = 1.
[0]
Current mode
*
[1]
Voltage mode
®
VLT
DriveMotor FCP 106 and FCM 106 Programming Guide
Function:
View the feedback resulting
from the selection of scaling
in parameter 3-02 Minimum
Reference and
parameter 3-03 Maximum
Reference.
Unused
Unused
Digital input term. 29
Digital input term. 27
Digital input term. 19
Digital input term. 18
Unused
MG03N102 - Rev. 2013-12-02
16-64 Analog Input AI54
Range:
Function:
1
[0 - 20 ]
View the actual value at input 54.
*
16-65 Analog Output AO42 [mA]
Range:
Function:
0 mA
[0 - 20 mA] View the actual value at output 42 in mA.
*
The value shown reflects the selection in
6-90 Terminal 42 Mode and 6-91 Terminal 42
Analog Output.
16-66 Digital Output
Range:
Function:
0
[0 -
View the binary value of all digital outputs.
*
15 ]
Definition:
X: Not used
0: Low
1: High
XX
None used
X0
Terminal 42 not used, Terminal 45
low
X1
Terminal 42 not used, Terminal 45
High
0X
Terminal 42 low, Terminal 45 not
used
0
Terminal 42 low, Terminal 45 low
1
Terminal 42 low, Terminal 45 high
1X
Terminal 42 high, Terminal 45 not
used
10
Terminal 42 high, Terminal 45 low
11
Terminal 42 high, Terminal 45 high
Table 4.10 Binary Value of Digital Outputs
16-67 Pulse Input #29 [Hz]
Range:
Function:
0
[0 - 130000 ] View the actual frequency rate on terminal
*
29.
16-71 Relay Output [bin]
Range:
Function:
0
[0 - 65535 ] View the setting of the relay.
*
Bits definition:
Bit 0~2
Bit 3
Bit 4
Bit 5~15
Table 4.11 Relay Setting
Unused
Relay 02
Relay 01
Unused
83
4
4