Danfoss VLT DriveMotor FCP 106 Programming Manual page 65

Hide thumbs Also See for VLT DriveMotor FCP 106:
Table of Contents

Advertisement

Parameters
6-92 Terminal 42 Digital Output
Option:
[0]
No operation
[1]
Control Ready
[2]
Drive ready
[3]
Drive ready/remote control
[4]
Standby / no warning
[5]
Drive running
[6]
Running / no warning
[7]
Run in range/no warning
[8]
Run on ref/no warning
[9]
Alarm
[10]
Alarm or warning
[12]
Out of current range
[13]
Below current, low
[14]
Above current, high
[16]
Below speed, low
[17]
Above speed, high
[19]
Below feedback, low
[20]
Above feedback, high
[21]
Thermal warning
[22]
Ready, no thermal warning
[23]
Remote, ready, no thermal
warning
[24]
Ready, Voltage OK
[25]
Reverse
[26]
Bus OK
[32]
Mech brake ctrl
[35]
External Interlock
[36]
Control word bit 11
[37]
Control word bit 12
[41]
Below reference, low
[42]
Above ref, high
[45]
Bus Control
[60]
Comparator 0
[61]
Comparator 1
[62]
Comparator 2
[63]
Comparator 3
[64]
Comparator 4
[65]
Comparator 5
[70]
Logic rule 0
[71]
Logic rule 1
[72]
Logic rule 2
[73]
Logic rule 3
[74]
Logic rule 4
[75]
Logic rule 5
[80]
SL digital output A
®
VLT
DriveMotor FCP 106 and FCM 106 Programming Guide
Function:
Select the function of
Terminal 42 as an analog
current output. See also
6-90 Terminal 42 Mode. See
parameter 5-40 Function
Relay for description of the
choices.
MG03N102 - Rev. 2013-12-02
6-92 Terminal 42 Digital Output
Option:
[81]
SL digital output B
[82]
SL digital output C
[83]
SL digital output D
[160] No alarm
[161] Running reverse
[165] Local ref. active
[166] Remote ref. active
[167] Start command activ
[168] Drive in hand mode
[169] Drive in auto mode
[193] Sleep Mode
[194] Broken Belt Function
[196] Fire Mode
[198] Drive Bypass
6-93 Terminal 42 Output Min Scale
Range:
Function:
0 %
[0 - 200
Scale for the minimum output (0 or 4 mA) of
*
%]
the analog signal at Terminal 42. Set the value
to be the percentage of the full range of the
variable selected in 6-91 Terminal 42 Analog
Output.
6-94 Terminal 42 Output Max Scale
Range:
Function:
100
[0 -
Scale for the maximum output (20 mA) of the
%
200
scaling at Terminal 42. Set the value to be the
*
%]
percentage of the full range of the variable
selected in 6-91 Terminal 42 Analog Output.
Current
(mA)
20
0/4
0%
Analogue
output
Min Scale
par. 6-93
Illustration 4.14 Output Max Scale
6-96 Terminal 42 Output Bus Control
Range:
0
[0 - 16384 ]
*
6-98 Drive Type
Range:
0
[0 - 0 ]
*
Function:
Analogue
Variable
100%
Output
for
Max Scale
output
par. 6-94
example:
Power
Function:
Function:
63
4
4