The Pke Field - Danfoss VLT AQUA Drive FC 200 Operating Instructions Manual

Low harmonic drive
Hide thumbs Also See for VLT AQUA Drive FC 200:
Table of Contents

Advertisement

RS-485 Installation and Set...
Text block
The text block is used to read or write texts via the data
block.
STX
LGE

7.3.7 The PKE Field

The PKE field contains two sub-fields: Parameter command
and response AK, and Parameter number PNU:
7
7
AK
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Parameter commands master ⇒ slave
Bit no.
15
14
0
0
0
0
0
0
0
0
1
1
1
1
1
1
Response slave ⇒master
Bit no.
15
14
0
0
0
0
0
0
0
1
1
1
142
VLT AQUA Low Harmonic Drive Operating Instructions
ADR
PKE
IND
PKE
IND
PWE
high
PNU
Parameter command
13
12
0
0
No command
0
1
Read parameter value
1
0
Write parameter value in RAM (word)
1
1
Write parameter value in RAM (double word)
0
1
Write parameter value in RAM and EEprom (double word)
1
0
Write parameter value in RAM and EEprom (word)
1
1
Read/write text
Response
13
12
0
0
No response
0
1
Parameter value transferred (word)
1
0
Parameter value transferred (double word)
1
1
Command cannot be performed
1
1
text transferred
MG20T202 - VLT
Ch1
Ch2
Chn
Bits no. 12-15 transfer parameter commands from master
to slave and return processed slave responses to the
master.
PWE
low
®
is a registered Danfoss trademark
PCD1
PCD2
BCC