Parameters
13-52 SL Controller Action
Array [20]
Option:
Function:
[3]
Select set-up 2
Changes the active set-up
(parameter 0-10 Active Set-up) to '2'.
[10] Select preset
Selects preset reference 0.
ref 0
[11] Select preset
Selects preset reference 1.
ref 1
[12] Select preset
Selects preset reference 2.
ref 2
[13] Select preset
Selects preset reference 3.
ref 3
[14] Select preset
Selects preset reference 4.
ref 4
[15] Select preset
Selects preset reference 5.
ref 5
[16] Select preset
Selects preset reference 6.
ref 6
[17] Select preset
Selects preset reference 7. If the active
ref 7
preset reference is changed, it will merge
with other preset reference commands
coming from either the digital inputs or
via a fieldbus.
[18] Select ramp 1
Selects ramp 1
[19] Select ramp 2
Selects ramp 2
[22] Run
Issues a start command to the frequency
converter.
[23] Run reverse
Issues a start reverse command to the
frequency converter.
[24] Stop
Issues a stop command to the frequency
converter.
[25] Qstop
Issues a quick stop command to the
frequency converter.
[26] DC Brake
Issues a DC stop command to the
frequency converter.
[27] Coast
The frequency converter coasts
immediately. All stop commands including
the coast command stop the SLC.
[28] Freeze output
Freezes the output frequency of the
frequency converter.
[29] Start timer 0
Starts timer 0, see parameter 13-20 SL
Controller Timer for further description.
[30] Start timer 1
Starts timer 1, see parameter 13-20 SL
Controller Timer for further description.
[31] Start timer 2
Starts timer 2, see parameter 13-20 SL
Controller Timer for further description.
[32] Set digital out
Any output with 'digital output 1' selected
A low
is low (off).
®
VLT
DriveMotor FCP 106 and FCM 106 Programming Guide
13-52 SL Controller Action
Array [20]
Option:
[33] Set digital out
B low
[34] Set digital out
C low
[35] Set digital out
D low
[38] Set digital out
A high
[39] Set digital out
B high
[40] Set digital out
C high
[41] Set digital out
D high
[60] Reset Counter
A
[61] Reset Counter
B
[70] Start Timer 3
[71] Start Timer 4
[72] Start Timer 5
[73] Start Timer 6
[74] Start Timer 7
MG03N102 - Rev. 2013-12-02
Function:
Any output with 'digital output 2' selected
is low (off).
Any output with 'digital output 3' selected
is low (off).
Any output with 'digital output 4' selected
is low (off).
Any output with 'digital output 1' selected
is high (closed).
Any output with 'digital output 2' selected
is high (closed).
Any output with 'digital output 3' selected
is high (closed).
Any output with 'digital output 4' selected
is high (closed).
Resets Counter A to zero.
Resets Counter B to zero.
Starts timer 3, see parameter 13-20 SL
Controller Timer for further description.
Starts timer 4, see parameter 13-20 SL
Controller Timer for further description.
Starts timer 5, see parameter 13-20 SL
Controller Timer for further description.
Starts timer 6, see parameter 13-20 SL
Controller Timer for further description.
Starts timer 7, see parameter 13-20 SL
Controller Timer for further description.
4
4
75