Parameters

4 Parameters
4.1 Main Menu - Operation and Display -
Group 0
Parameters related to the fundamental functions of the
frequency converter, function of the LCP keys and configu-
4
4
ration of the LCP display.
4.1.1 0-0* Basic Settings
0-01 Language
Option:
[0]
English
*
[1]
Deutsch
[2]
Francais
[3]
Dansk
[4]
Spanish
[5]
Italiano
[28]
Bras.port
[255] No Text
0-03 Regional Settings
Option:
[0] Interna-
tional
[1] North
America
0-04 Operating State at Power-up
Option:
[0]
Resume
*
34
VLT
Function:
Defines the language to be used in the display.
Function:
NOTICE
This parameter cannot be adjusted while
the motor is running.
To meet the needs for different default settings
in different parts of the world,
parameter 0-03 Regional Settings is implemented
in the frequency converter. The selected setting
influences the default setting of the motor
nominal frequency.
Sets default value of parameter 1-23 Motor
Frequency [50 Hz].
Sets the default value of parameter 1-23 Motor
Frequency to 60 Hz.
Function:
Select the operating mode upon reconnection
of the frequency converter to mains voltage
after power down when operating in Hand
(local) mode.
Resumes operation of the frequency converter
maintaining the same local reference and the
same start/stop condition (applied by [Hand
On]/[Off] on the LCP or Hand Start via a digital
®
DriveMotor FCP 106 and FCM 106 Programming Guide
0-04 Operating State at Power-up
Option:
[1]
Forced
stop,
ref=old
0-06 GridType
Option:
[10]
380-440V/
50Hz/IT-grid
[11]
380-440V/50Hz/
Delta
[12]
380-440V/50Hz
[20]
440-480V/
50Hz/IT-grid
[21]
440-480V/50Hz/
Delta
[22]
440-480V/50Hz
[110] 380-440V/
60Hz/IT-grid
[111] 380-440V/60Hz/
Delta
[112] 380-440V/60Hz
[120] 440-480V/
60Hz/IT-grid
[121] 440-480V/60Hz/
Delta
MG03N102 - Rev. 2013-12-02
Function:
input as before the frequency converter was
powered down.
Uses saved reference [1] to stop the frequency
converter but at the same time retain the local
speed reference in memory before powering
down. After mains voltage is reconnected and
after receiving a start command (pressing [Hand
On] key or using her Hand Start command via a
digital input) the frequency converter restarts
and operates at the retained speed reference.
Function:
Select the grid type of the supply
voltage/frequency.
NOTICE
Not all choices are supported in all
power sizes.
IT grid is a supply mains, where there
are no connections to ground.
Adjust the position of the RFI switch to
match the grid type (refer toVLT
DriveMotor FCP 106 and FCM 106
Operating Instructions)
Delta is a supply mains where the
secondary part of the transformer is
delta connected and one phase is
connected to ground.
®