7.4.7 The PKE Field

7
7
The PKE field contains two sub-fields: Parameter command and response AK, and Parameter number PNU:
AK
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Bits no. 12-15 transfer parameter commands from master to slave and return processed slave responses to the master.
Parameter commands master ⇒ slave
Bit no.
15
14
0
0
0
0
0
0
0
0
1
1
1
1
1
1
128
VLT
ADR
PKE
IND
ADR
PKE
IND
PKE
IND
PWE
high
PNU
Parameter command
13
12
0
0
No command
0
1
Read parameter value
1
0
Write parameter value in RAM (word)
1
1
Write parameter value in RAM (double word)
0
1
Write parameter value in RAM and EEprom (double word)
1
0
Write parameter value in RAM and EEprom (word)
1
1
Read/write text
MG11BB02 - VLT
®
HVAC Drive Design Guide
PWE
PWE
high
low
Ch1
Ch2
Chn
PWE
low
®
is a registered Danfoss trademark
PCD1
PCD2
PCD1
PCD2
BCC
BCC