Danfoss VLT DriveMotor FCP 106 Programming Manual page 37

Hide thumbs Also See for VLT DriveMotor FCP 106:
Table of Contents

Advertisement

Parameters
0-06 GridType
Option:
Function:
[122] 440-480V/60Hz
0-07 Auto DC Braking
Option: Function:
Protective function against overvoltage at coast.
NOTICE
Can cause PWM when coasted.
[0]
Off Function is not active.
[1]
On
Function is active.
*
4.1.2 0-1* Define and Set Up Operations
A complete set of all parameters controlling the frequency
converter is called a set-up. The frequency converter
contains 2 set-ups: Set-up1 and Set-up2. Furthermore, a
fixed set of factory settings can be copied into one or
more set-ups.
Some of the advantages of having more than one set-up
in the frequency converter are:
Run motor in one set-up (Active Set-up) while
updating parameters in another set-up (Edit Set-
up)
Connect various motors (one at a time) to
frequency converter. Motor data for various
motors can be placed in different set-ups.
Rapidly change settings of frequency converter
and/or motor while motor is running e.g. Ramp
time or preset references) via bus or digital
inputs.
The Active Set-up can be set as Multi Set-up, where the
active set-up is selected via input on a digital input
terminal and/or via the bus control word.
Use parameter 0-51 Set-up Copy to copy a set-up to the
other set-ups. To avoid conflicting settings of the same
parameter within 2 different set-ups, link the set-ups
together using parameter 0-12 Link Setups. Stop the
frequency converter before switching between set-ups
where parameters marked 'not changeable during
operation' have different values.
Parameters which are 'not changeable during operation'
are marked FALSE in chapter 6 Parameter Lists.
0-10 Active Set-up
Option:
Function:
Select the set-up in which the frequency
converter is to operate.
[1]
Set-up 1
Set-up 1 is active.
*
®
VLT
DriveMotor FCP 106 and FCM 106 Programming Guide
0-10 Active Set-up
Option:
[2]
Set-up 2
[9]
Multi Set-
up
0-11 Programming Set-up
Option:
[1]
Set-up 1
[2]
Set-up 2
[9]
Active Set-up Edit parameters in the set-up selected via
*
0-12 Link Setups
Option:
[0]
Not
linked
[20]
Linked
*
4.1.3 0-3* LCP Custom Readout and Display
Text
It is possible to customise the display elements for various
purposes.
Custom Readout
The calculated value to be displayed is based on settings
in parameter 0-30 Custom Readout Unit,
parameter 0-31 Custom Readout Min Value (linear only),
parameter 0-32 Custom Readout Max Value,
parameter 4-14 Motor Speed High Limit [Hz] and actual
speed.
MG03N102 - Rev. 2013-12-02
Function:
Set-up 2 is active.
Is used for remote selection of set-ups using
digital inputs and the serial communication
port. This set-up uses the settings from
parameter 0-12 Link Setups.
Function:
The number of the set-up being edited is
displayed in the LCP, flashing.
Edit Set-up 1
Edit Set-up 2
digital I/Os
Function:
If the set-ups are not linked, a change between
them is not possible while the motor is running.
When selecting a different setup for operation,
the set-up change does not occur until the
motor is coasted
Copies "not changeable during operation"
parameters from one set-up to the other. It is
possible to switch set-up while the motor is
running.
4
4
35