Parameters
14-64 Dead Time Compensation Zero Current Level
For a long motor cable, set this parameter to [0] to minimize the
motor-torque ripple.
Option:
[0]
Disabled
*
[1]
Enabled
14-65 Speed Derate Dead Time Compensation
Range:
Expres-
[Expres-
sionlimit(50)
sionlimit(20) -
Hz
Expres-
*
sionlimit(1000) Hz]
4.10.7 14-9* Fault Settings
Fault Customisation Settings
14-90 Fault Level
Use this parameter to customise fault levels. Setting the
parameter value may change 1-73 Flying Start.
Option:
[3]
Trip lock
*
[4]
Trip with delayed reset
[5]
Flystart
4.11 Main Menu - Drive Information - Group
15
Parameter group containing frequency converter
information such as operating data, hardware configu-
ration and software versions.
4.11.1 15-0* Operating Data
15-00 Operating hours
Range:
Function:
0 h
[0 - 0x7fffffff. h] View how many hours the frequency
*
converter has run. The value is saved
when the frequency converter is turned
off.
15-01 Running Hours
Range:
Function:
0 h
[0 -
View how many hours the motor has run.
*
0x7fffffff. h]
Reset the counter in parameter 15-07 Reset
Running Hours Counter. The value is saved
when the frequency converter is turned off.
®
VLT
DriveMotor FCP 106 and FCM 106 Programming Guide
Function:
Function:
Deadtime compensation
level is reduced linearly in
relation to output
frequency. The maximum
level is set by 14-07 Dead
Time Compensation Level.
The minimum output
frequency level is defined in
14-65 Speed Derate Dead
Time Compensation.
Function:
MG03N102 - Rev. 2013-12-02
15-02 kWh Counter
Range:
Function:
0 kWh
[0 -
View the output power of the frequency
*
65535
converter in kWh as a mean value over 1
kWh]
hour. Reset the counter in
parameter 15-06 Reset kWh Counter.
15-03 Power Up's
Range:
Function:
0
[0 - 2147483647 ] View the number of times the frequency
*
converter has been powered up.
15-04 Over Temp's
Range:
Function:
0
[0 - 65535 ] View the number of frequency converter
*
temperature faults which have occurred.
15-05 Over Volt's
Range:
Function:
0
[0 - 65535 ] View the number of frequency converter
*
overvoltages which have occurred.
15-06 Reset kWh Counter
Option:
Function:
NOTICE
Pres [OK] to reset.
[0]
Do not reset
*
[1]
Reset counter Select [1] Reset and press [OK] to reset the
kWh counter to zero (see
parameter 15-02 kWh Counter).
15-07 Reset Running Hours Counter
Option:
Function:
[0]
Do not reset
*
[1]
Reset counter Select [1] Reset counter and press [OK] to
reset Running Hours counter
(parameter 15-01 Running Hours) to zero (see
also parameter 15-01 Running Hours).
4.11.2 15-3* Alarm Log
Parameters in this group are array parameters, where up to
10 fault logs can be viewed. [0] is the most recent logged
data, and [9] the oldest. Error codes, values, and time
stamp can be viewed for all logged data.
15-30 Alarm Log: Error Code
Range:
Function:
0
[0 - 255 ] View the error code and look up its meaning in
*
chapter 5 Diagnostics and Troubleshooting.