Parameters
4.2.2 1-10 - 1-12 Motor Selection
NOTICE
This parameter group cannot be adjusted while the
motor is running.
The following parameters are active ('x') depending on the
setting of 1-10 Motor Construction
1-10 Motor Construction
1-00 Configuration Mode
1-03 Torque Characteristics
1-06 Clockwise Direction
1-14 Damping Gain
1-15 Low Speed Filter Time Const.
1-16 High Speed Filter Time Const.
1-17 Voltage filter time const.
1-20 Motor Power [kW]
1-22 Motor Voltage
1-23 Motor Frequency
1-24 Motor Current
1-25 Motor Nominal Speed
parameter 1-26 Motor Cont. Rated
Torque
parameter 1-29 Automatic Motor
Adaption (AMA)
1-30 Stator Resistance (Rs)
1-33 Stator Leakage Reactance (X1)
1-35 Main Reactance (Xh)
1-37 d-axis Inductance (Ld)
1-39 Motor Poles
1-40 Back EMF at 1000 RPM
1-52 Min Speed Normal Magnetising
[Hz]
1-60 Low Speed Load Compensation
1-61 High Speed Load Compensation
1-62 Slip Compensation
1-63 Slip Compensation Time Constant
1-64 Resonance Dampening
1-65 Resonance Dampening Time
Constant
1-66 Min. Current at Low Speed
1-71 Start Delay
1-72 Start Function
1-73 Flying Start
1-80 Function at Stop
1-82 Min Speed for Function at Stop
[Hz]
parameter 1-90 Motor Thermal
Protection
2-00 DC Hold Current
®
VLT
DriveMotor FCP 106 and FCM 106 Programming Guide
2-01 DC Brake Current
2-02 DC Braking Time
2-04 DC Brake Cut In Speed [Hz]
2-06 Parking Current
parameter 2-07 Parking Time
2-10 Brake Function
2-16 AC brake Max. Current
2-17 Over-voltage Control
4-10 Motor Speed Direction
4-12 Motor Speed Low Limit [Hz]
[0]
[1] PM
4-14 Motor Speed High Limit [Hz]
Asynchron
Motor
4-18 Current Limit
non
4-19 Max Output Frequency
salient
4-58 Missing Motor Phase Function
x
x
14-40 VT Level
x
14-41 AEO Minimum Magnetisation
x
x
parameter 30-22 Locked Rotor
x
Detection
x
parameter 30-23 Locked Rotor
x
Detection Time [s]
x
x
Table 4.2 Parameters Activated by Setting of1-10 Motor Construction
x
x
x
1-10 Motor Construction
x
x
Select the motor construction type. Other parameters will be
x
x
changed when changing motor type selection
x
Option:
[0]
x
x
[1]
x
x
x
x
x
x
x
NOTICE
x
Motor construction can either be asynchronous or
x
permanent magnet (PM) motor, non-salient SPM.
x
x
1-11 Motor Selection
x
Option:
x
[0] Default Motor
x
x
x
x
x
x
x
1-12 Motor ID
x
x
Range:
x
x
Default Motor
x
x
x
x
x
MG03N102 - Rev. 2013-12-02
Function:
Asynchron
For asynchronous motors.
*
PM, non salient SPM For permanent magnet (PM) motors
with surface mounted (non salient)
magnets. Refer to parameters 1-14 to
1-17 for optimising the motor
operation
Function:
Automatically sets the manufacturer's settings
Selection
for the selected motor.
Setting the parameter value might change
these parameters. Other parameters will also
change, when changing motor type selection
Function:
[0 - 0 ] Displays motor name according to the
*
selected motor in par.1-11 Motor
Selection
x
x
x
x
x
x
x
x
x
x
4
4
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
39