Parameters
13-01 Start Event
Option:
Function:
Low and parameter 4-51 Warning Current
High)
[4]
On reference
The motor runs at reference speed.
[7]
Out of current
The motor current is outside the range set
range
in parameter 4-18 Current Limit.
[8]
Below I low
The motor current is lower than set in
parameter 4-50 Warning Current Low.
[9]
Above I high
The motor current is higher than set in
parameter 4-51 Warning Current High.
[16]
Thermal
The thermal warning turns on when the
warning
temperature exceeds the limit in the
motor, the frequency converter or the
thermistor.
[17]
Mains out of
range
[18]
Reversing
The frequency converter is reversing.
[19]
Warning
A warning is present.
[20]
Alarm (trip)
An alarm is present.
[21]
Alarm (trip
A trip lock alarm is present.
lock)
[22]
Comparator 0
Use the result of comparator 0 in the logic
rule.
[23]
Comparator 1
Use the result of comparator 1 in the logic
rule.
[24]
Comparator 2
Use the result of comparator 2 in the logic
rule.
[25]
Comparator 3
Use the result of comparator 3 in the logic
rule.
[26]
Logic rule 0
Use the result of logic rule 0 in the logic
rule.
[27]
Logic rule 1
Use the result of logic rule 1 in the logic
rule.
[28]
Logic rule 2
Use the result of logic rule 2 in the logic
rule.
[29]
Logic rule 3
Use the result of logic rule 3 in the logic
rule.
[33]
Digital input
Use the value of DI18 in the logic rule
DI18
(High = TRUE).
[34]
Digital input
Use the value of DI19 in the logic rule
DI19
(High = TRUE).
[35]
Digital input
Use the value of DI27 in the logic rule
DI27
(High = TRUE).
[36]
Digital input
Use the value of DI29 in the logic rule
DI29
(High = TRUE).
®
VLT
DriveMotor FCP 106 and FCM 106 Programming Guide
13-01 Start Event
Option:
[39]
Start
command
*
[40]
Drive stopped
[42]
Auto Reset
Trip
[50]
Comparator 4
[51]
Comparator 5
[60]
Logic rule 4
[61]
Logic rule 5
[83]
Broken Belt
13-02 Stop Event
Option:
[0]
False
[1]
True
[2]
Running
[3]
In range
[4]
On reference
[7]
Out of current
range
[8]
Below I low
[9]
Above I high
[16]
Thermal
warning
[17]
Mains out of
range
MG03N102 - Rev. 2013-12-02
Function:
This event is TRUE if the frequency
converter is started (either via digital
input, field bus or other).
This event is TRUE if the frequency
converter is stopped or coasted (either via
digital input, fieldbus or other).
This event is TRUE if the frequency
converter is tripped (but not trip-locked)
and an Automatic Reset is issued.
Use the result of comparator 4 in the logic
rule.
Use the result of comparator 5 in the logic
rule.
Use the result of logic rule 4 in the logic
rule.
Use the result of logic rule 5 in the logic
rule.
A broken belt condition has been
detected. This function must be enabled
in parameter 22-60 Broken Belt Function.
Function:
Select the condition (TRUE or FALSE)
which deactivates the Smart Logic
Controller.
Enters the fixed value of FALSE in the
logic rule.
Enters the fixed value TRUE in the logic
rule.
See parameter 13-01 Start Event for
further description.
See parameter 13-01 Start Event for
further description.
See parameter 13-01 Start Event for
further description.
See parameter 13-01 Start Event for
further description.
See parameter 13-01 Start Event for
further description.
See parameter 13-01 Start Event for
further description.
See parameter 13-01 Start Event for
further description.
See parameter 13-01 Start Event for
further description.
4