Parameters
6-72 Terminal 45 Digital Output
Option:
[61]
Comparator 1
[62]
Comparator 2
[63]
Comparator 3
[64]
Comparator 4
[65]
Comparator 5
[70]
Logic rule 0
4
4
[71]
Logic rule 1
[72]
Logic rule 2
[73]
Logic rule 3
[74]
Logic rule 4
[75]
Logic rule 5
[80]
SL digital output A
[81]
SL digital output B
[82]
SL digital output C
[83]
SL digital output D
[160] No alarm
[161] Running reverse
[165] Local ref. active
[166] Remote ref. active
[167] Start command activ
[168] Drive in hand mode
[169] Drive in auto mode
[193] Sleep Mode
[194] Broken Belt Function
[196] Fire Mode
[198] Drive Bypass
6-73 Terminal 45 Output Min Scale
Range:
0 %
[0 - 200 %]
*
0.0%
[0.0-200.0%]
*
6-74 Terminal 45 Output Max Scale
Range:
100 %
[0 - 200 %]
*
62
®
VLT
DriveMotor FCP 106 and FCM 106 Programming Guide
Function:
Function:
Scale for the minimum output (0 or 4 mA)
of the analog signal at Terminal 45. Set the
value to be the percentage of the full
range of the variable selected in
parameter 6-71 Terminal 45 Analog Output.
Function:
Scale for the maximum output (20 mA)
of the analog signal at Terminal 45. Set
the value to be the percentage of the
full range of the variable selected in
parameter 6-71 Terminal 45 Analog
Output.
6-74 Terminal 45 Output Max Scale
Range:
100.0%
[0.0-200.0%]
*
6-76 Terminal 45 Output Bus Control
Range:
0
[0 - 16384 ]
*
4.7.5 6-9* Analog/Digital Output 42
Parameters for configuring the limits for analog/digital
output Terminal 42. Analog outputs are current outputs:
0/4-20 mA. Resolution on analog outputs is 12 bit. Analog
output terminals can also be set-up as digital output.
6-90 Terminal 42 Mode
Option:
[0]
0-20 mA
*
[1]
4-20 mA
[2]
Digital Output
6-91 Terminal 42 Analog Output
Option:
[0]
No operation
*
[100] Output frequency 0-100 Hz
[101] Reference
[102] Feedback
[103] Motor Current
[106] Power
[139] Bus Control
MG03N102 - Rev. 2013-12-02
Function:
Current
(mA)
20
0/4
0%
Analogue
Analogue
100%
output
Output
Min Scale
Max Scale
par. 6-73
par. 6-74
Illustration 4.13 Output Max Scale
Function:
Function:
Set Terminal 42 to act as analog output or
as digital output.
Function:
Select the function of Terminal 42 as an
analog current output. See also
6-90 Terminal 42 Mode.
Min
- Max
Ref.
Ref.
Min
- Max
FB
FB
0-I
max
0-P
nom
0-100%
Variable
for
output
example:
Power