Diagnostics and Troubleshoo...

5.4 Extended Status Words

Bit
Hex
Dec
0
1
1
1
2
2
2
4
4
3
8
8
4
10
16
5
20
32
6
40
64
7
80
128
8
100
256
9
200
512
10
400
1024
11
800
2048
12
1000
4096
13
2000
8192
14
4000
16384
15
8000
32768
16
10000
65536
17
20000
131072
18
40000
262144
19
80000
524288
20
100000
1048576
21
200000
2097152
22
400000
4194304
23
800000
8388608
24
1000000
16777216
25
2000000
33554432
26
4000000
67108864
27
8000000
134217728
28
10000000
268435456
29
20000000
536870912
30
40000000
1073741824
31
80000000
2147483648
Table 5.5 Extended Status Words
0: this alarm is not used in FCP 106
®
VLT
DriveMotor FCP 106 and FCM 106 Programming Guide
parameter 16
parameter 16-95
-94 Ext.
Ext. Status
Status Word
Word 2
Ramping
Off
AMA running
Hand/Auto
Start CW/CCW
0
0
0
0
0
Feedback
high
0
Feedback low
0
Output
current high
Control Ready
Output
current low
Drive Ready
Output
frequency
high
Quick Stop
Output
frequency low
DC Brake
0
Stop
0
0
Freeze Output
Braking
Request
0
Freeze Output
OVC active
Jog Request
AC brake
Jog
0
Start request
0
Start
Reference
high
0
Reference low
Start Delay
Local Ref./
Remote Ref.
Sleep
0
Sleep boost
0
Running
0
Bypass
0
Fire Mode
0
External Interlock
Firemodelimi-
0
texceed
0
FlyStart Active
0
0
0
0
Database
busy
0
MG03N102 - Rev. 2013-12-02

5.5 Troubleshooting

WARNING/ALARM 2, Live zero error
This warning or alarm only appears if programmed in
6-01 Live Zero Timeout Function. The signal on one of the
analog inputs is less than 50% of the minimum value
programmed for that input. Broken wiring or faulty device
sending the signal can cause this condition.
Troubleshooting
Check connections on all the analog input
terminals. Control card terminals 53 and 54 for
signals, terminal 55 common. MCB 101 terminals
11 and 12 for signals, terminal 10 common. MCB
109 terminals 1, 3, 5 for signals, terminals 2, 4, 6
common).
Check that the frequency converter programming
and switch settings match the analog signal type.
Perform input terminal signal test.
WARNING/ALARM 3, No motor
No motor has been connected to the output of the
frequency converter.
WARNING/ALARM 4, Mains phase loss
A phase is missing on the supply side, or the mains
voltage imbalance is too high. This message also appears
for a fault in the input rectifier on the frequency converter.
Options are programmed at 14-12 Function at Mains
Imbalance.
Troubleshooting
Check the supply voltage and supply currents to
the frequency converter.
WARNING/ALARM 7, DC overvoltage
If the intermediate circuit voltage exceeds the limit, the
frequency converter trips after a time.
Troubleshooting
Connect a brake resistor
Extend the ramp time
Change the ramp type
Activate the functions in 2-10 Brake Function
Increase 14-26 Trip Delay at Inverter Fault
If the alarm/warning occurs during a power sag,
use kinetic back-up (14-10 Mains Failure)
WARNING/ALARM 8, DC under voltage
If the DC-link voltage drops below the undervoltage limit,
the frequency converter checks if a 24 V DC backup supply
is connected. If no 24 V DC backup supply is connected,
the frequency converter trips after a fixed time delay. The
time delay varies with unit size.
Troubleshooting
Check that the supply voltage matches the
frequency converter voltage.
Perform input voltage test.
5