Parameters
24-10 Drive Bypass Function
Option:
Function:
if the timer expires before reset attempts
have completed.
24-11 Drive Bypass Delay Time
Range:
Function:
0 s
[0 -
Programmable in 1 s increments. Once the Bypass
*
600 s]
Function is activated in accordance with the
setting in parameter 24-10 Drive Bypass Function,
the Bypass Delay Timer begins to operate. If the
frequency converter has been set for a number of
restart attempts, the timer continues to run while
the frequency converter tries to restart. Should the
motor have restarted within the time period of the
Bypass Delay Timer, then the timer is reset.
Should the motor fail to restart at the end of the
Bypass Delay Time, the Drive Bypass relay is
activated, which has been programmed for Bypass
in parameter 5-40 Function Relay.
Where no restart attempts are programmed, the
timer runs for the delay period set in this
parameter and then activates the Drive Bypass
relay, which has been programmed for Bypass in
parameter 5-40 Function Relay, Function Relay.

4.17 Main Menu - Special Features - Group

30
30-22 Locked Rotor Detection
Locked Rotor Detection for PM-Motor
Option:
[0]
Off
[1]
On
30-23 Locked Rotor Detection Time [s]
Locked Rotor Detection Time for PM-Motor
Range:
0.10 s
[0.05 - 1 s]
*
®
VLT
DriveMotor FCP 106 and FCM 106 Programming Guide
Function:
Function:
MG03N102 - Rev. 2013-12-02
4
4
91