Goodrive350 series high-performance multi-function inverter
Function
Name
code
detection value This parameter is used to set the speed deviation
Speed deviation
P11.15
detection time
Automatic
frequency-reducti
P11.16
on during voltage
drop
Proportional
coefficient of
P11.17
voltage regulator
during
undervoltage stall
Integral
coefficient of
P11.18
voltage regulator
during
undervoltage stall
Proportional
coefficient of
P11.19
current regulator
during
undervoltage stall
Integral
coefficient of
P11.20
current regulator
during
undervoltage stall
Detailed parameter description
detection value.
This parameter is used to set the speed deviation
detection time.
Note: Speed deviation protection will be invalid if
P11.15 is set to 0.0.
Actual detection
value
Set detection
value
t1<t2, so the inverter continues running
t2=P11.15
Setting range: 0.0–10.0s
0–1
0: Invalid
1: Valid
0–1000
0–1000
0–1000
0–2000
-179-
Speed
t1
t2
Time t
Running
Fault output
Chapter 6
Default
value
1.0s
dEu
0
100
40
25
150
Modi
fy