Goodrive350 series high-performance multi-function inverter
Function
Name
code
DC brake after
stop
DC brake current
P01.11
of stop
DC brake time of
P01.12
stop
Deadzone time of
P01.13
forward/reverse
rotation
Forward/reverse
P01.14
rotation
switch-over mode
P01.15
Stop speed
Stop speed
P01.16
detection mode
P01.17
Stop speed
Detailed parameter description
stop): Before the DC brake, the inverter will block
output, and after the demagnetization time elapses,
DC brake will start. This function is used to prevent
overcurrent fault caused by DC brake during high
speed.
DC brake current after stop: it means the DC brake
force applied, the larger the current, the stronger the
DC brake effect.
Acceleration
P01.04
P13.14
P01.23
Setting range of P01.09: 0.00Hz–P00.03 (max.
output frequency)
Setting range of P01.10: 0.00–30.00s
Setting range of P01.11: 0.0–100.0%
Setting range of P01.12: 0.0–50.0s
This function code refers to the transition time of the
threshold set by P01.14 during setting
forward/reverse rotation of the inverter, as shown
below.
Output frequency f
Forward
Starting
frequency
Setting range: 0.0–3600.0s
0: Switch over after zero frequency
1: Switch over after starting frequency
2: Switch over after passing stop speed and delay
0.00–100.00Hz
0: Set value of speed (the only detection mode valid
in SVPWM mode)
1: Detection value of speed
0.00–100.00s
-126-
P01.09
P13.15
Constant speed
Deceleration
P01.12
P01.10
In running
Switch over after
starting frequency
Switch over after
zero frequency
Deadzone
Reverse
time
Chapter 6
Default
value
0.0%
Time t
0.00s
0.0s
Time t
0
0.50Hz
0
0.50s
Modi
fy
○
○
○
◎
◎
◎
◎