This output operates the dehumidify coil for dehumidification.
Output is either Time Proportioning or On/Off
L11 Dehumidify On
L12 Dehumidify Off
LEV 1
Dehumidify Coil vs. Drier Logic (Input 2)
Control Parameters
Channel 2 Proportional Band Cooling
Reset for Channel 2 Cooling
Rate for Channel 2 Cooling
Cycle Time for Channel 2 Cooling
Rate Band for Channel 2 Cooling
Synergy Controller Technical Manual, Revision H
Dehumidify Coil
Percent dehumidify required to enable dehumidify device
Percent humidity required to turn off dehumidify device
Selects the Drier Device when Input 2 is closed,
otherwise the Dehumidify Coil is selected.
When closed and when LEV 1 is set to Use Drier,
disables the dehumidify coil and uses the Drier device
instead.
Default Value:
40
0.1
0
7
0
Range:
0 - 50 Degrees C
0 - 9.9 Repeats/minute
0 - 9.9 Minutes
1 - 60 Seconds
0 - 7 Seconds
Page 207