Name/function
Exit Mode,
cont.
Explanation
Final Door Set
 Use this option to complete internal arming of a partition by closing the last exit
door. This door has a detector with zone type "Final Door". When the door is
closed, the partition is internally armed once the settle time has expired.
 Note that the exit time for this option is unlimited, i.e. when the zone is closed
(closed door) the alarm panel waits until this zone is opened and then closed
again before internally arming.
 The alarm panel saves the start time of internal arming (and not the internal arm-
ing itself) in the log book.
 Do not attempt to use a PIR zone as a "Final Door" for a partition. PIR wireless
detectors has a "lock" time period after each arming, in order to save battery
power. If a partition is armed (or internally armed), a PIR detector may still be
locked. During this time it cannot send signals to complete the arming process.
Instant Set
 The partition is internally armed immediately without any acoustic warning tone. If
the partition has been internally armed, an acoustic confirmation sounds.
 Note: This option does not comply with BS8243:2010.
Silent Set
 The partition is internally armed after the exit time has expired. Under "Exit time"
select the corresponding time. However, no warning tone sounds during this time.
If the partition has been internally armed, an acoustic confirmation sounds. The
alarm panel saves the start time in the log book.
 During entry time the acoustic warning tone can be heard.
 Note: This option does not comply with BS8243:2010.
Lock Set
 The "Lock Set" mode affects both internal arming and disarming of the partition.
 For this mode, a detector with zone type "Lock Set" and a detector with zone type
"Final Door" must be assigned at the last exit door. The detector with zone type
"Lock Set" is operated with a lock switch contact on a suitable lock.
Internally arming the partition
 The user must first start the arming sequence using the user code, proximity
keyfob or remote control.
The alarm panel then sounds the exit tone and saves the start time in the log
book.
If the "Final Door" zone is open, the alarm panel emits a continuous exit tone.
The exit tone sounds until the user:
a) closes the last exit door and then
b) locks the door and therefore activates the lock switch contact.
After the lock switch contact is activated, the partition is internally armed once the
settle time has expired.
The "Final Door" zone is also converted into a "Normal Alarm" zone.
The alarm panel saves the activation of the "Lock Set" zone in the log book.
Configuration
99