Configuration
Name/function
Exit Mode,
cont.
100
Explanation
Disarming the partition
 The user unlocks the door and therefore activates the lock switch contact. The
"Lock Set" zone is opened. The alarm panel saves the activation of the "Lock Set"
zone in the log book. The original "Final Door" zone which was converted into a
"Normal Alarm" zone is switched back into a "Final Door" zone. The entry time
starts when the door is opened. The entry tone sounding at this point is different
from a normal entry tone.
 If the user locks the door again without starting the entry time, the alarm panel re-
mains armed and the "Final Door" zone is converted again into a "Normal Alarm"
zone. The alarm panel stops the warning tone.
 To comply with BS8243, "After Entry" must be set to "Never" in order to prevent
confirmation.
Exit Terminate
Internally arming the partition
 The user must first start the arming sequence. Then the user ends the arming
process after existing the monitoring area.
 The user can start the arming sequence using the user code, proximity keyfob or
remote control. (Note: arming with remote control must not be set to "Instant", In-
staller Mode->System->User Access->Remote Inst. Set).
 The user ends arming by activating a zone with type "Exit Terminate" (see expla-
nation of zone types).
 Note that the exit time is unlimited with this option, i.e. the alarm panel waits until
it receives the signal to end the arming process before it arms. The alarm panel
emits the exit tone during this time. The alarm panel saves the start time of arm-
ing (and not the arming itself) in the log book. The partition is armed after the set-
tle time has expired.
Disarming the partition
 The user can use the remote control. The user can also open the door. The "Final
Door" zone at this door starts the entry time. During entry time the user must dis-
arm the partition using the user code or proximity keyfob at the alarm panel or
control device. (The last method is not compliant with BS8243 clause 6.4.)
As SA (partition) 1
This option is available for partitions 2, 3 and 4. If this option is selected, the alarm
panel uses the same type as for partition 1.