Name/function
Supervision
Explanation (checkbox)
Dropdown selection field for alarm system response for supervision
If a wireless detector has had no contact with the alarm control panel for more than
20 min, the alarm panel creates a log entry: "RF warning". The alarm panel also
prevents the system from being armed. If a user overrides this warning and arms
the alarm panel, the log entry "RF warning overridden" is generated.
If a wireless detector has had no contact with the alarm panel for more than 2 h,
corresponding processes are activated as follows:
Alarm panel is armed
Disabled
No response
 Log book entry of this
Fault
event
 No display and no warning
tones
 "RF Supervision" or "RF Fault"
outputs are activated
 Tampering alarm
Tamper Ac-
 Supervision is reported
tivated
Note:
If "Tamp as Tamp-Only" is disa-
bled, the "Supervision" or "Fault"
outputs are also activated.
If no tamper channel is assigned
in FF, an "unconfirmed alarm" is
sent.
Note
The "Tamper" option is required in Grade 2 systems in order to comply with
EN 50131-1:2006+A1:2009.
If the "Tamper" option is used along with the following setting:
System -> User Reset -> System Tampers = No
the user cannot reset the system.
Configuration
Alarm panel is disarmed
No response
 Log book entry of this event
 Display and warning tones
 "RF Supervision" or "RF Fault"
outputs are activated
 Tampering alarm
 Supervision is reported
Note
If "Tamp as Tamp-Only" is disa-
bled, the "Supervision" or "Fault"
outputs are also activated.
If no tamper channel is assigned
in FF, an "unconfirmed alarm" is
sent.
133