Type
User Defined
Smoke Sensor Reset
PIR Set Latch
Combination Output 1
...
Combination Output 10
Explanation
An output of this type can be controlled remotely via dif-
ferent user-defined components such as remote control,
control panel or alarm panel.
The "Switch by user" and "configure by user" options
grant the user permissions for the configuration of the out-
put in the user menu view.
The "Polarity" button can be used to invert the switching
statuses.
If the output should only be switched for a specific time
(pulse behaviour), then un-tick the "Continuous" checkbox
and set the desired duration.
The output can also be assigned a time plan, which speci-
fies when it should be activated or deactivated. The "Con-
tinuous" checkbox must be ticked for this. Then set the
switching on time, the switching off time and select the
desired days of the week.
The output can also be switched by the occurrence of
events. On the "Events" tab, you can set up to 3 events.
The list contains all possible output types.
This output is always activated (0 V) except when a user
confirms a fire alarm.
After this confirmation, the alarm panel deactivates the
output for 3 seconds.
The output type is designed to facilitate interaction with
low voltage reset connections on wired smoke detectors.
Note that there are also smoke detectors common on the
market that require a second confirmation in order to be
reset (detectors that require time to reset the alarm con-
tacts after the reset pulse).
This type requires the system or partition to have been
armed.
This output is deactivated when the system or partition is
disarmed or an alarm event occurs.
The output is activated for one second when either the
system is reset or installer mode is exited on the alarm
panel.
Note: if "Normal" polarity is selected, the output is actu-
ated with +12 V when activated and 0 V when deac-
tivated. Use the "Inverted" polarity to reverse the function
of this output.
An output of this type combines various events. Details on
this can be found in the "Combination Outputs" chapter.
Configuration
Can be assigned
to partitions
No
Yes
Yes