On the wireless or wired output, select the type "Combination output".
You have set up "Combination output 1". You can use this to enable "Wireless output 203" on the alarm panel. Assign
"Combination output 1" as the type for "Wireless output 203".
You have to select one mode for each "combination output". This mode can be ALL (AND) or ANY (OR).
For the AND mode, all inputs of the "combination output" have to be enabled for it to function.
For the OR mode, any inputs of the "combination output" may be enabled for it to function.
Example:
Requirement:
A wireless output should switch when a door (Zone 203) is open AND an installer has logged in in installer mode.
The solution:
Configure the wireless output with the type "Combination output 1" and configure "Combination output 1" as follows:
Combination output
Mode
1
ALL (AND)
Note
An input may be the output of another "combination output". However, you can only select "combination outputs" with
a number higher than the inputs.
For example, if the alarm panel supports 10 "combination outputs", and you specify "Combination output 8", you can
only use the outputs from "Combination output 9" and "Combination output 10" as inputs.
input
Input 1 type = Installer on site
Input 2 type = Zone follow (Zone 203)
Configuration